4-11
Chapter 4
For parameter configuration
[Ab-01] to [Ab-25]
Frequency scale conversion monitor [dA-06]
Code/Name
Range (unit)
Initial value
Ab-01 Frequency
conversion gain
0.01 to 100.00
1.00
The visualized “Output frequency scale conversion
monitor[dA-06]” is equal to the “Output frequency
monitor[dA-01]” multiplied by the “Frequency
conversion gain[Ab-01]”.
Multi-speed command
Code/Name
Range (unit)
Initial
value
Ab-03 Multi-speed operation
selection
00(Binary(16 speeds))/
01(Bit(8 speeds))
00
Ab110 Multi-speed 0 setting,
1st-motor
0.00 to 590.00(Hz) *1)
0.00
Ab-11 Multi-speed 1 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-12 Multi-speed 2 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-13 Multi-speed 3 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-14 Multi-speed 4 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-15 Multi-speed 5 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-16 Multi-speed 6 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-17 Multi-speed 7 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-18 Multi-speed 8 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-19 Multi-speed 9 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-20 Multi-speed 10 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-21 Multi-speed 11 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-22 Multi-speed 12 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-23 Multi-speed 13 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-24 Multi-speed 14 setting
0.00 to 590.00(Hz) *1)
0.00
Ab-25 Multi-speed 15 setting
0.00 to 590.00(Hz) *1)
0.00
*1) The actual setting range is limited to the maximum frequency setting
([Hb105/205] [Hd105/205]).
For the 16 speeds selection, set [Ab-03]=00 for assigning
the intelligent terminals 003[CF1] to 006[CF4] makes
available the use of the speeds 0 to 15.
Multispeed
CF4
CF3
CF2
CF1
Speed 0
OFF
OFF
OFF
OFF
Speed 1
OFF
OFF
OFF
ON
Speed 2
OFF
OFF
ON
OFF
Speed 3
OFF
OFF
ON
ON
Speed 4
OFF
ON
OFF
OFF
Speed 5
OFF
ON
OFF
ON
Speed 6
OFF
ON
ON
OFF
Speed 7
OFF
ON
ON
ON
Speed 8
ON
OFF
OFF
OFF
Speed 9
ON
OFF
OFF
ON
Speed 10
ON
OFF
ON
OFF
Speed 11
ON
OFF
ON
ON
Speed 12
ON
ON
OFF
OFF
Speed 13
ON
ON
OFF
ON
Speed 14
ON
ON
ON
OFF
Speed 15
ON
ON
ON
ON
[Ab210][AC-01] to [AC-02]
For the 8 speeds selection, set [Ab-03]=01 assigning the
intelligent terminals 007[SF1] to 013[SF7] makes
available the use of the speeds 0 to 7.
Multispeed
SF7
SF6
SF5
SF4
SF3
SF2
SF1
Speed 0
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Speed 1
-
-
-
-
-
-
ON
Speed 2
-
-
-
-
-
ON
OFF
Speed 3
-
-
-
-
ON
OFF
OFF
Speed 4
-
-
-
ON
OFF
OFF
OFF
Speed 5
-
-
ON
OFF
OFF
OFF
OFF
Speed 6
-
ON
OFF
OFF
OFF
OFF
OFF
Speed 7
ON
OFF
OFF
OFF
OFF
OFF
OFF
2nd motor When Intelligent Input terminal 024[SET] is enabled.
Code/Name
Range (unit)
Initial
value
Ab210 Multi-speed 0 setting,
2nd-motor
Same as Ab110
Input method for Accel/Decel time
Code/Name
Range (unit)
Initial
value
AC-01
Acceleration/Deceleration
time input source selection
00(Parameter setting)/
01(Option 1)/
02(Option 2)/
03(Option 3)/
04(Function EzSQ)
00
[AC-01] changes the reference source for the Accel/Decel
command.
Individual Accel/Decel time for Multispeed
Code/Name
Range (unit)
Initial
value
AC-02
Acceleration/
Deceleration selection
00(Common etting)/
01(Multi stage sccel/decel)
00
When [AC-02]=00, the Accel/Decel time settings
[AC120][AC122] or [AC124][AC126] are enable.
2-stage Accel/Decel time function is set with parameters
[AC115] to [AC117].
When [AC-02]=01, the Accel/Decel time [AC-30] to
[AC-88] for each multispeed control (from speed 1 to
15) are enabled.
Even if [AC-02]=01, while in Multspeed-0 command,
Accel/Decel time setting [AC120] [AC122] or
Accel/Decel time setting [AC124] [AC126] are enabled.
[CA-64]/[CA-66] takes precedence during the input
terminal 020[FUP]/021[FDN] function. And [AH-78]
takes precedence during the PID soft start function.