4-18
Chapter 4
For parameter configuration
[AH-01] to [AH-06]
PID1 function
Code/Name
Range (unit)
Initial value
AH-01 PID1 enable
00(Disable)/
01(Enable)/
02(Enable (with inverted
output)
00
The PID1 function is enabled with the above parameter.
If [AH-01]=01 when the PID output reaches negative value, the
PID output is limited to 0.
If [AH-01]=02 when the PID output reaches negative value, the
PID output lets out an inverted output.
When the PID output is negative, the motor will rotate in the
contrary direction.
If input terminal 041[PID] is ON, the PID control is disabled
and the PID target value becomes the frequency reference.
Code/Name
Range (unit)
Initial
value
AH-03
unit selection for PID1
Refer <unit table>
of the end of this
chapter.
01
AH-04 PID1 adjustment (0%)
-10000 to 10000
0
AH-05 PID1 adjustment (100%)
-10000 to 10000
10000
AH-06 PID1 Adjustment
(decimal point position)
0 to 4
2
The unit and display data related to the output of the PID
control can be changed.
PID1 is capable of 3 target value inputs and 3 feedback inputs,
and various operations can be performed with [AH-50] and
[AH-54].
■ When AH-50 = 01 to 04 ( + , - , ×, / ) , the operation target is
PID1 set-point 1 (select from [AH-07] and [AH-10] to [AH-40])
and PID1 set-point 2 (selected with [AH-42]).
[AH-07] to [AH-50]
Code/Name
Range (unit)
Initial
value
AH-07 PID1 set-point 1 input source
selection
0013 *2)
09
AH-10 PID1 set-point-1 setting
-100.00 to
100.00(%)
*1)
0.00
AH-12 PID1 multistage set-point 1
0.00
AH-14 PID1 multistage set-point 2
0.00
AH-16 PID1 multistage set-point 3
0.00
AH-18 PID1 multistage set-point 4
0.00
AH-20 PID1 multistage set-point 5
0.00
AH-22 PID1 multistage set-point 6
0.00
AH-24 PID1 multistage set-point 7
0.00
AH-26 PID1 multistage set-point 8
0.00
AH-28 PID1 multistage set-point 9
0.00
AH-30 PID1 multistage set-point 10
0.00
AH-32 PID1 multistage set-point 11
0.00
AH-34 PID1 multistage set-point 12
0.00
AH-36 PID1 multistage set-point 13
0.00
AH-38 PID1 multistage set-point 14
0.00
AH-40 PID1 multistage set-point 15
0.00
AH-42 PID1 set-point 2 input source
selection
00 to 13 *2)
00
AH-44 PID1 set-point 2 setting
-100.00 to
100.00(%) *1)
0.00
AH-46 PID1 set-point 3 input source
selection
00 to 13 *2)
0.00
AH-48 PID1 set-point 3 setting
-100.00 to
100.00(%) *1)
0.00
AH-50 PID1 set-point calculation
symbol selection
01(Addition)
02(Subtraction)
03(Multiplication)
04(Division)
05(Minimum
deviation)
06(Maximum
deviation)
01
*1) Range will depend on the parameters [AH-04], [AH-05] and [AH-06].
*2) 00(Not used )/01(Terminal[Ai1])/02(Terminal[Ai2])/
03(Terminal[Ai3])/04(Terminal[Ai4])/05(Terminal[Ai5])/
06(Terminal[Ai6])/07(Parameter setting)/08(RS485)/09(Option-1)/
10(Option-2)/11(Option-3)/12(Pulse train input (internal)/
13(Pulse train input (option)
If Input terminal 051[SVC1] to 054[SVC4] are used, the PID1
set-point 1 can be changed for the Multistage.
Multistage value
SVC4
SVC3
SVC2
SVC1
AH-10
OFF
OFF
OFF
OFF
AH-12
OFF
OFF
OFF
ON
AH-14
OFF
OFF
ON
OFF
AH-16
OFF
OFF
ON
ON
AH-18
OFF
ON
OFF
OFF
AH-20
OFF
ON
OFF
ON
AH-22
OFF
ON
ON
OFF
AH-24
OFF
ON
ON
ON
AH-26
ON
OFF
OFF
OFF
AH-28
ON
OFF
OFF
ON
AH-30
ON
OFF
ON
OFF
AH-32
ON
OFF
ON
ON
AH-34
ON
ON
OFF
OFF
AH-36
ON
ON
OFF
ON
AH-38
ON
ON
ON
OFF
AH-40
ON
ON
ON
ON
Code/Name
Range (unit)
Initial value
AH-02 PID1 deviation inversion
00(Disable)/
01(Enable)
00
PID1
target value
[db-42]
PID1 set-point 1[ AH-10]
RS485
communication
Option 1 to 3
Pulse train
(internal)
Pulse train
(option)
[AH-07]
multistage set-point 1 to 15
[AH-12] to [AH-40]
Analog input 1 to 6
Not used
[SVC1-4]
[AH-50]
+, -, x, ÷
[AH-42]
01 to 06
07
08
09 to 11
12
13
07
PID1 set-point 2[ AH-44]
07
01
00
[AH-46]
00
PID1 set-point 3[AH-48]
00
PID1
deviation
inversion
[AH-02]
PID
deviation
PID target
value
Feefeedback
+
00
01
-
×(-1)