For parameter configuration
AH-71 PID1 output variable
・[AH-71] Limits the output range of the PID.
If [AH-71] = 0.00 the limit is disabled.
AH-72 PID1 over deviation
level
・When the PID deviation pass over the±[AH-72], the
output terminal 045[OD] Deviation over for PID control
is ON.
AH-73 Turn-off level for the
PID1 feedback compare signal
AH-74 Turn-on level for the PID1
feedback compare signal
・When the PID feedback cross over the [AH-73] level, the
output terminal 046[FBV] is OFF. If the PID feedback
crosses under the [AH-74] level, 046[FBV] is turned ON.
[AH-75] to [AH-82]
PID soft start function
AH-75 PID soft start function enable
AH-76 PID soft start target level
AH-78 Acceleration time setting
for PID soft start function
AH-80 PID soft start time
AH-81 PID soft start error
detection enable
00(Disable)/
01(Enable:
Error[E120])
02(Enable:
Warning[SSE])
AH-82 PID soft start error
detection level
*1) Ver2.01 and older, setting range is 0.00 to 100.0
・In order to start the shockless PID, normal operation is
performed with the base frequency × [AH-76] as the
target frequency from the start of operation to the set
time of [AH-80].
・The acceleration time at soft start can be set with
[AH-78].
・When an error is judged, the operation changes
depending on the setting of [AH-81] PID soft start
error detection enable.
- If [AH-81] is 00, nothing is done.
- If [AH-81] is 01, the abnormal state will trip with
[E120] PID start error after the set time of [AH-80]
has elapsed.
- If [AH-81] is 02, the output terminal 093[SSE] PID
soft start error signal turns ON after the abnormal
state has passed for the [AH-80] setting time.
- Output terminal 093[SSE] signal is turned ON while
the inverter is in running.
According to [AH-78] acceleration
PID Output variable range