4-20
Chapter 4
For parameter configuration
[AH-71] to [AH-74]
Code/Name
Range (unit)
Initial value
AH-71 PID1 output variable
0.00 to 100.00(%)
0.00
[AH-71] Limits the output range of the PID.
If [AH-71] = 0.00 the limit is disabled.
Code/Name
Range (unit)
Initial value
AH-72 PID1 over deviation
level
0.00 to 100.00(%)
3.00
When the PID deviation pass over the±[AH-72], the
output terminal 045[OD] Deviation over for PID control
is ON.
Code/Name
Range (unit)
Initial
value
AH-73 Turn-off level for the
PID1 feedback compare signal
0.00 to 100.00(%)
100.00
AH-74 Turn-on level for the PID1
feedback compare signal
0.00 to 100.00(%)
0.00
When the PID feedback cross over the [AH-73] level, the
output terminal 046[FBV] is OFF. If the PID feedback
crosses under the [AH-74] level, 046[FBV] is turned ON.
[AH-75] to [AH-82]
PID soft start function
Code/Name
Range (unit)
Initial
value
AH-75 PID soft start function enable
00(Disable)/
01(Enable)
00
AH-76 PID soft start target level
0.00 to 100.00(%)
100.00
AH-78 Acceleration time setting
for PID soft start function
0.00 to 3600.00(s)
30.00
AH-80 PID soft start time
0.00 to 600.00(s)
*1)
0.00
AH-81 PID soft start error
detection enable
00(Disable)/
01(Enable:
Error[E120])
02(Enable:
Warning[SSE])
00
AH-82 PID soft start error
detection level
0.00 to 100.00(%)
0.00
*1) Ver2.01 and older, setting range is 0.00 to 100.0
In order to start the shockless PID, normal operation is
performed with the base frequency × [AH-76] as the
target frequency from the start of operation to the set
time of [AH-80].
The acceleration time at soft start can be set with
[AH-78].
When an error is judged, the operation changes
depending on the setting of [AH-81] PID soft start
error detection enable.
- If [AH-81] is 00, nothing is done.
- If [AH-81] is 01, the abnormal state will trip with
[E120] PID start error after the set time of [AH-80]
has elapsed.
- If [AH-81] is 02, the output terminal 093[SSE] PID
soft start error signal turns ON after the abnormal
state has passed for the [AH-80] setting time.
- Output terminal 093[SSE] signal is turned ON while
the inverter is in running.
[AH-80]
PID
operation
[AH-76]
According to [AH-78] acceleration
Output frequency
Time
PID feedback
PID Target value
ON
PID feedback (%)
Time(s)
0%
[AH-73]
Output erminal
046[FBV]
Run command
[AH-74]
ON
ON
ON
PID deviation (%)
Time(s)
0%
[AH-72]
Output
terminal
045[OD]
ON
ON
[AH-72]
PID Output (%)
Time(s)
PID
Target
value
[AH-71]
PID Output variable range
[AH-71]