4-24
Chapter 4
For parameter configuration
[AJ-41] to [AJ-52]
PID4 function
Code/Name
Range (unit)
Initial
value
AJ-41 PID4
enable
00(Disable)/01(Enable)/
02(Enable (with inverted output)
00
The PID4 function is enabled with the above parameter.
If [AJ-41]=01 when the PID output reaches a negative
value, the PID output is limited to 0.
If [AJ-41]=02 when the PID output reaches a negative
value, the PID output lets out an inverted output.
By turning on the 047[PID4] terminal, the PID4 output
becomes 0.
Code/Name
Range (unit)
Initial value
AJ-42 PID4 deviation inversion
00(Disable)/
01(Enable)
00
PID4 deviation can be reversed.
Code/Name
Range (unit)
Initial
value
AJ-43 PID4 unit selection
Refer <unit table> of
the end of this
chapter.
01
AJ-44
PID4 scale adjustment (0%)
-10000 to 10000
0
AJ-45
PID4 scale adjustment (100%)
-10000 to 10000
10000
AJ-46 PID4 scale adjustment
(decimal point position)
0 to 4
2
You can switch the display data and the display unit
involved in the output of the PID control by the
calculation.
Code/Name
Range (unit)
Initial
value
AJ-47 PID4 set-point input
source selection
00 to 13 *1)
07
AJ-50 PID4 set-point setting
-100.00 to 100.00(%)
*2)
0.00
*2) Range will depend on the parameters [AJ-44] [AJ-45] [AJ-46]
When PID4 target value input is selected, if the selected
is the parameter setting, [AJ-50] is enabled.
Code/Name
Range (unit)
Initial
value
AJ-52 PID4 feedback input
source selection
00 to 06/08 to 13 *1)
01
Selects the PID4 feedback reference.
*1) 00(Not used)/01(Terminal[Ai1])/02(Terminal[Ai2])/03(Terminal[Ai3])/
04(Terminal[Ai4])/05(Terminal[Ai5])/06(Terminal[Ai6])/07(Parameter
setting)/08(RS485)/09(Option-1)/10(Option-2)/11(Option-3)/12(Pulse train
input (internal)/13(Pulse train input (option)
[AJ-53] to [AJ-59]
Code/Name
Range (unit)
Initial
value
AJ-53 PID4 proportional gain
0.0 to 100.0
1.0
AJ-54 PID4 integral time constant
0.0 to 3600.0(s)
1.0
AJ-55 PID4 derivative gain
0.00 to
100.00(s)
0.00
The PID4 gains are set by the above parameters.
If input terminal 048[PIDC4] is active (ON), the value of
the integral constant is cleared. If it is done while the
inverter is in running, the driving condition may
become unstable.
Code/Name
Range (unit)
Initial value
AJ-56 PID4 output range
0.00 to 100.00(%)
0.00
[AJ-56] Limits the output range of the PID. If [AJ-56]
=0.00 the limit is disabled.
Code/Name
Range (unit)
Initial value
AJ-57 PID4 over deviation
level
0.00 to 100.00(%)
3.00
When the PID deviation pass over ±[AJ-57], the output
terminal 091[OD4] is activated.
Code/Name
Range (unit)
Initial
value
AJ-58 Turn-off level for the PID4
feedback compare signal
0.00 to 100.00(%)
100.00
AJ-59 Turn-on level for the PID4
feedback compare signal
0.00 to 100.00(%)
0.00
When the PID feedback cross over the [AJ-58] level, the
output terminal 092[FBV4] is OFF. If the PID feedback
crosses under the [AJ-59] level, 092[FBV4] is turned
ON.
PID feedback (%)
Time(s)
0%
[AJ-58]
092[FBV4]
RUN command
[AJ-59]
ON
ON
ON
PID deviation (%)
Time(s)
0%
[AJ-57]
Output
terminal
091[OD4]
ON
ON
[AJ-57]
PID output (%)
Time(s)
PID
Target
value
[AJ-56]
PID output range
[AJ-56]
]
PID4 deviation
inversion
[AJ-42]
PID
deviation
PID target
value
+
00
01
-
×(-1)
Feedback
value