For parameter configuration
[AJ-41] to [AJ-52]
PID4 function
00(Disable)/01(Enable)/
02(Enable (with inverted output)
・The PID4 function is enabled with the above parameter.
・If [AJ-41]=01 when the PID output reaches a negative
value, the PID output is limited to 0.
・If [AJ-41]=02 when the PID output reaches a negative
value, the PID output lets out an inverted output.
・By turning on the 047[PID4] terminal, the PID4 output
becomes 0.
AJ-42 PID4 deviation inversion
・PID4 deviation can be reversed.
AJ-43 PID4 unit selection
Refer <unit table> of
the end of this
chapter.
AJ-44
PID4 scale adjustment (0%)
AJ-45
PID4 scale adjustment (100%)
AJ-46 PID4 scale adjustment
(decimal point position)
・You can switch the display data and the display unit
involved in the output of the PID control by the
calculation.
AJ-47 PID4 set-point input
source selection
AJ-50 PID4 set-point setting
*2) Range will depend on the parameters [AJ-44] [AJ-45] [AJ-46]
・When PID4 target value input is selected, if the selected
is the parameter setting, [AJ-50] is enabled.
AJ-52 PID4 feedback input
source selection
・Selects the PID4 feedback reference.
*1) 00(Not used)/01(Terminal[Ai1])/02(Terminal[Ai2])/03(Terminal[Ai3])/
04(Terminal[Ai4])/05(Terminal[Ai5])/06(Terminal[Ai6])/07(Parameter
setting)/08(RS485)/09(Option-1)/10(Option-2)/11(Option-3)/12(Pulse train
input (internal)/13(Pulse train input (option)
[AJ-53] to [AJ-59]
AJ-53 PID4 proportional gain
AJ-54 PID4 integral time constant
AJ-55 PID4 derivative gain
・The PID4 gains are set by the above parameters.
・If input terminal 048[PIDC4] is active (ON), the value of
the integral constant is cleared. If it is done while the
inverter is in running, the driving condition may
become unstable.
・[AJ-56] Limits the output range of the PID. If [AJ-56]
=0.00 the limit is disabled.
AJ-57 PID4 over deviation
level
・When the PID deviation pass over ±[AJ-57], the output
terminal 091[OD4] is activated.
AJ-58 Turn-off level for the PID4
feedback compare signal
AJ-59 Turn-on level for the PID4
feedback compare signal
・When the PID feedback cross over the [AJ-58] level, the
output terminal 092[FBV4] is OFF. If the PID feedback
crosses under the [AJ-59] level, 092[FBV4] is turned
ON.
PID4 deviation
inversion
[AJ-42]