For parameter configuration
[bA-70] to [bA-71][bA201] to [bA249]
Cooling-fan operation
bA-70 Cooling fan
control method
selection
00(Always ON)/
01(While inverter operates)/
02(Depends on temperature)
bA-71 Clear
accumulated cooling fan
run time monitor
・The Inverter cooling fan can be stopped.
・If you change the cooling-fan, assigning [bA-71]=01 you
will be able to clear the accumulated operation time.
2nd motor When Intelligent Input terminal 024[SET] is enabled.
bA201 Upper frequency limit source selection,
2nd-motor
bA202 Upper Frequency limit, 2nd-motor
bA203 Lower Frequency limit , 2nd-motor
bA210 Torque limit selection, 2nd-motor
bA211 Torque limiting parameters mode selection,
2nd-motor
bA212 Torque limit 1 (Forward drive), 2nd-motor
bA213 Torque limit 2 (Reverse regenerative),
2nd-motor
bA214 Torque limit 3 (Reverse drive), 2nd-motor
bA215 Torque limit 4 (Forward regenerative),
2nd-motor
bA216 Torque limit LADSTOP selection, 2nd-motor
bA220 Overcurrent suppression enable,
2nd-motor
bA221 Overcurrent suppression level, 2nd-motor
bA222 Overload restriction 1 mode selection,
2nd-motor
bA223 Overload restriction 1 active level,
2nd-motor
bA224 Overload restriction 1 action time,
2nd-motor
bA226 Overload restriction 2 mode selection,
2nd-motor
bA227 Overload restriction 2 active level,
2nd-motor
bA228 Overload restriction 2 action time,
2nd-motor
bA240 Overvoltage suppression enable,
2nd-motor
bA241 Overvoltage suppression active level,
2nd-motor
bA242 Overvoltage suppression active time,
2nd-motor
bA244 Constant DC bus voltage control P gain,
2nd-motor
bA245 Constant DC bus voltage control I gain,
2nd-motor
bA246 Over magnetization function selection,
2nd_motor
bA247 Over magnetization function output filter
time constant, 2nd-motor
bA248 Over magnetization function voltage gain,
2nd-motor
bA249 Over magnetization function level setting,
2nd-motor
[bb101] to [bb-23]
Reduction of electromagnetic sound
bb101 Carrier
frequency setting,
1st-motor
・400V SH1-007H to SH1-550H
[Ub-03]=
02(ND): 0.5 to 16.0(kHz)
01(LD): 0.5 to 12.0(kHz)
00(VLD): 0.5 to 10.0(kHz)
・400V SH1-750H or above
[Ub-03]=
02(ND): 0.5 to 10.0(kHz)
01(LD): 0.5 to 8.0(kHz)
00(VLD):0.5 to 8.0(kHz)
bb102 Sprinkle
carrier pattern
selection, 1st-motor
00(Disable)/
01(Enable: Patern-1)/
02(Enable: Patern-2)/
03(Enable: Patern-3)
bb103 Automatic
carrier reduction
selection, 1st-motor
00(Disable)/
01(Enable: Current)/
02(Enable: Temperature)
・To decrease high frequency electromagnetic noise, [bb101]
should be set small. To lower motor sound loudness, [bb101]
has to be set bigger.
・The carrier frequency may be internally limited depending on
the setting of Load type selection [Ub-03].
※(SH1-03410-H(SH1-1600H)toSH1-04810-H(SH1-2200H)support only
ND(normal duty)and LD(low duty)).
・For the sake of the inverter protection, the Automatic carrier
reduction [bb103] decreases the carrier in certain cases.
Reset operation after error event
bb-10 Automatic
error reset selection
00(Disable)/
01(If RUN command is OFF)
02(After set time)
bb-11 Alarm signal
selection at automatic
error reset
bb-12 Automatic
error reset wait time
bb-13 Automatic
error reset number
・Adjustment of the automatic reset that follows an error
event. In the case that RUN command was on
execution, after resetting, the motor re-operates
according to the setting of [bb-41] Restart mode after
RS release.
Retry/trip setting in error event
bb-20 Number of retries after
instantaneous power failure
bb-21 Number of retries after
under voltage
bb-22 Number of retries after
overcurrent
bb-23 Number of retries after over
voltage
・Set the number of times to retry after each error.
・If 0 is set, as soon as an error occurs, it will trip.
・To retry, set the value of these parameters other than 0.