4-28
Chapter 4
For parameter configuration
[bb-24] to [bb-42]
Restart mode after instantaneous power
failure/under-voltage error
Code/Name
Range (unit)
Initial
value
bb-24 Restart mode selection after
instantaneous power
failure/under-voltage error
*1)
01
bb-25 Instantaneous power failure
allowed time
0.3 to 25.0(s)
1.0
bb-26 Retry wait time after
instantaneous power
failure/under-voltage error
0.3 to
100.0(s)
0.3
bb-27 Enable instantaneous power
failure/ under-voltage trip while in stop
status
00(Disable)/
01(Enable)/
02(Disable at
Stop/Decel. stop)
00
bb-28 Restart mode selection after
an overcurrent error
*1)
01
bb-29 Retry wait time after an
overcurrent error
0.3 to
100.0(s)
0.3
bb-30 Restart mode selection after
an overvoltage error
*1)
01
bb-31 Retry wait time after an
overvoltage error
0.3 to
100.0(s)
0.3
*1) 00(Restart at 0Hz)/01(Restart with matching frequency)/02(Restart with active
frequency matching)/03(Detect speed)/04(Decelerate and stop with matching
frequency and then trip)
Regarding the restart, after the waiting time is completed the selected restart
method is carried out.
Restart mode after FRS/RS
Code/Name
Range (unit)
Initial
value
bb-40
Restart mode after FRS release
00(Restart at 0Hz)/
01(Restart with matching
frequency)/
02(Restart with active
frequency matching)/
03(Detect speed) *2)
00
bb-41
Restart mode after RS release
00
*2) This function requires encoder feedback to the P1-FB option or to the input
terminals [A]/[B] assigned 103[PLA]/104[PLB].
When using input terminal 032[FRS] and 028[RS], restart mode can be selected.
By [bb-40], input terminal 032 [FRS] Free run ON and restart operation
after free run at stop are selected.
[bb-41] selects not only the operation after input terminal 028[RS] reset, but also
the restart operation after reset by power supply shutdown and the restart
operation after reset release at trip.
When the input terminal 035[CS] commercial power supply change is turned ON,
the inverter will be in free running state, and restart with matching frequency
will be performed after [bb-26] time has elapsed.
For more information, Please contact your supplier or local Hitachi
inverter sales office.
Minimum level of frequency matching
Code/Name
Range (unit)
Initial value
bb-42 Frequency
matching minimum restart
frequency
0.00 to 590.00(Hz)
0.00
The matching frequency function adopts the motor frequency for a
shockless start-up.
If at the restart the frequency is under the [bb-42] frequency, a 0Hz restart
will be used instead.
[bb-43] to [bb-64]
Active frequency matching
Code/Name
Range (unit)
Initial value
bb-43 Active frequency
matching restart level
Inverter rated
current
×(0.2 to 2.0)(A)
Inverter
rated
current×1.0
bb-44 Active frequency
matching restart
constant(speed)
0.10 to 30.00(s)
0.50
bb-45
Active frequency matching
restart constant (voltage)
0.10 to 30.00(s)
0.50
bb-46
OC-supress level at active
frequency matching
Inverter rated
current
×(0.0 to 2.0)(A)
Inverter
rated current
× 1.0
bb-47 Active frequency
matching restart speed
selection
00(Output
frequency at
shut down)/
01(Maximum
frequency)/
02(Setting
frequency)
00
bb-50 Frequency matching
filter gain *3)
0 to 1000(%)
50
*3) [bb-50] is a parameter added to Ver2.03 or later.
If the actual rotation of the motor does not match the reference
frequency, this function is a restart method that lowers the starting
voltage so that the output current does not exceed [bb-43] and reduces
the reference frequency to match the motor speed.
Overcurrent level
Code/Name
Range (unit)
Initial value
bb160 Over current
detection level, 1st-motor
Inverter rated ND
current × (0.2 to 2.2)
(A)
Inverter ND
rated current
× 2.2(A)
The motor protection level for overcurrent can be set.
In the case of a permanent magnet motor, set this parameter lower
than the motor demagnetizing level.
Overvoltage warning
Code/Name
Range (unit)
Initial value
bb-61 Power supply over
voltage selection
00(Warning)/
01(Error)
00
bb-62 Power supply over
voltage level setting
(400V Class)
600.0820.0(V)
(400V Class)
780.0
When the power supply suffers an overvoltage and if the DC bus
voltage is higher than the value in [bb-62], a warning is issued in
accordance with [bb-61].
If [bb-61] is 01, the output terminal 081 [OVS]"Overvoltage power
Supply" signal turns on and trips with [E015] error.
If [bb-61] is 00, only the output terminal 081[OVS] signal is ON.
Selection of Ground fault detection
Code/Name
Range (unit)
Initial value
bb-64 Detect ground fault
selection
00(Disable)/
01(Enable)
01
Ground fault detection enable/disable is selectable.
Retry wait time
Free-run
Primary
cut off
Output
frequency(solid) and
Output voltage(dotted)
Motor speed
Setting
frequency [bb-42]
Start with
matching frequency
Output
current
Active frequency
matching restart
level [bb-43]
Frequency
[bb-47]
Deceleration time
[bb-44]
Setting time [bb-45]
(Note)
[bb-44] and [bb-45]
are the frequency
deceleration time and
voltage increase time
from 0Hz to the
maximum frequency.
Retry wait timeFW
Free-run (FRS)
Primary
cut off
Inverter
output
Motor speed
Lower limit
[bb-42]
Restart with matching
frequency