For parameter configuration
[bb-65] to [bb260]
Phase loss detection
bb-65 Input phase loss detection
enable
bb-66 Output phase loss
detection enable
bb-67 Output phase loss
detection sensitivity
・Above function detects the disconnection of the supply
RST input line and UVW output line.
Thermistor error detection
bb-70 Thermistor error level
Cb-40 Thermistor type selection
00(Disable)/
01(PTC)/02(NTC)
・The kind of thermistor specified in [Cb-40] must be attached to [TH]
terminal.
If [Cb-40] =01 or 02, error level must be set in [bb-70].
Over-speed detection
bb-80 Overs-peed detection level
bb-81 Over-speed detection time
・In vector control, when speed surpass “maximum
speed”×[bb-80] for more than the [bb-81] time, it will result in an
error.
Abnormal deviation in speed control
bb-82 Speed deviation error
mode selection
bb-83 Speed deviation error
detection level
bb-84 Speed deviation error
detection time
・In vector control, if the time which the speed deviation (absolute of
[dA-12]-[dA-08] ) is greater than the "maximum frequency setting" x
[bb-83] exceeds [bb-84] value , an error or warning will occur and the
output terminal 041[DSE] turn ON.
Abnormal deviation in position control
bb-85 Position deviation error
mode selection
bb-86 Position deviation error
detection level
bb-87 Position deviation error
detection level
・In position control, an error will occur if the time that position
deviation is greater than [bb-86] exceeds [bb-87].
・When the input terminal 072[PCLR] is turned ON, the position
deviation is cleared.
2nd motor When Intelligent Input terminal 024[SET] is enabled.
bb201 Carrier frequency setting,
2nd-motor
bb202 Sprinkle carrier pattern
selection, 2nd-motor
bb203 Automatic carrier reduction
selection, 2nd-motor
bb260 Overcurrent detection level,
2nd-motor
[bC110] to [bC125]
Electronic thermal protection
bC110 Electronic thermal
level setting, 1st-motor
Inverter rated
current ×
(0.0 to 3.0)(A)
Inverter
rated current
×1.0(A)
bC111
Electronic thermal characteristic
selection, 1st-motor
00(Reduced
torque (VT))/
01(Constant
torque (CT))/
02(Free setting)
00(JPN)/
01(EU)(USA)
(ASIA)(CHN)
bC112
Electronic thermal decrease
function enable, 1st-motor
bC113 Electronic thermal
decreasing time, 1st-motor
bC-14
Store electronic thermal counter
at power-off
bC120
Free electronic thermal
frequency-1, 1st-motor
bC121
Free electronic thermal
current-1, 1st-motor
Inverter rated
current ×
(0.0 to 3.0)(A)
bC122
Free electronic thermal
frequency-2, 1st-motor
bC123
Free electronic thermal
current-2, 1st-motor
Inverter rated
current ×
×(0.0 to 3.0)(A)
bC124
Free electronic thermal
frequency-3, 1st-motor
bC125
Free electronic thermal
current-3, 1st-motor
Inverter rated
current ×
×(0.0 to 3.0)(A)
・The setting of [bC112] enables subtraction of the motor's thermal
integration value. If [bC113] is lowered from the initial value, the risk
of motor burnout may increase, so set it appropriately according
to the heat dissipation characteristics of the motor.
(Example 1)
When [bC111] =00, Inverter rated current: 64A, [bC110] =64(A),
Base frequency [Hb104]=50Hz or 60Hz, Output frequency=20Hz
・In case of output frequency = 16Hz (base=50Hz) or 20Hz (base = 60hz),
the reduction scale is ×0.8, then the inverter will trip when the output
current of 120%(150%×0.8) flows continuously within 60s according
to the curve.
Inverter output
frequency (Hz)
Motor current (A)
(Ratio to the inverter
rated current)