*1) The rated input current is the value when the drive is operated in the rated output current. The value of the impedance at the supply side changes
due to the wiring, breaker, input reactor, etc.
*2) Make sure the following for Low Voltage Directive (LVD) compliant.
- Pollution degree 2, - Overvoltage category 3 (for 380 to 460Vac Input supply), - Overvoltage category 2 (for over 460Vac Input supply)
*3) The power supply capacity is the value of the rated output current at 440V. The value of the impedance at the supply side changes due to the wiring,
breaker, input reactor, etc.
*4) The setting range of carrier frequency [bb101] / [bb201] is limited according to the [Ub-03] setting(load type selection).
It is recommended to set the carrier frequency settings [bb101]/[bb201] equal or greater than the (maximum output frequency x 10)Hz.
For induction motor IM, it is recommended to set the carrier frequency to 2 kHz or more except V/f control. For synchronous motor
(SM)/Permanent magnet motor (PMM), it is recommended to set the carrier frequency to 8 kHz or more.
*5) The value is specified for the Hitachi standard motor controlled by the sensorless vector control when ND rating.
Torque characteristics may vary by the control system and the use of the motor.
*6) The key height of keypad is excluded from dimensions. When an option is connected, the depth is increased. Refer to the each optional Guide.
*7) The rated input current and power supply capacity of SH1-03410-H(SH1-1600H) and upper models are described under the condition that the
power factor improving reactor is installed.
*8) SH1-03410-H (SH1-1600H) to SH1-066000-H (SH1-3150H) support only ND (normal duty)/LD(low duty) double rating.