7.3 Common specifications (continue)
Intelligent output
terminals
Transistor output terminal 5, 1c contact relay 1 point
RUN(Running), FA1 to 5(Reached frequency signal), IRDY(Inverter ready), FWR(Forward rotation), RVR(Reverse rotation),
FREF(Frequency referenc=Keypad is selected ), REF(Run command = Keypad is selected), SETM(2nd-motor selected),
OPO(Option-Output), AL(Alarm signal), MJA(Major failure signal), OTQ(Over-torque) *7), IP(Instantaneous power failure),
UV(Undervoltage), TRQ(Torque limited), IPS(Decel. Power loss), RNT(Accumulated RUN time over), ONT(Accumulated
power-on time over), THM(Motor electronic thermal warning), THC(Iverter Electronic thermal warning), WAC(Capacitor
life warning), WAF(Cooling-fan life warning), FR(Starting contact signal), OHF(heat sink overheat warning),
LOC/LOC2(Low-current indication signal), OL/OL2(Overload warning signal 1/2), BRK(Brake release)/BER(Brake
error)/CON(Contactor control), ZS(Zero speed detection), DSE(Speed deviation over), PDD(Position deviation over),
POK(Positioning completed), PCMP(Pulse counter compare match output), OD/OD2/OD3/OD4(Output deviation for PID
control), FBV/FBV2/FBV3/FBV4(PID feedback comparison), NDc(Communication line disconnection),
Ai1Dc/Ai2Dc/Ai3Dc(Analog Ai1/Ai2/Ai3 disconnection), Ai4Dc/Ai5Dc/Ai6Dc(Option analog Ai4/Ai5/Ai6 disconnection),
WCAi1/WCAi2/WCAi3(Window comparator Ai1/Ai2/Ai3), WCAi4/WCAi5/WCAi6(Window comparator Ai4/Ai5/Ai6),LOG1
to 7(logical operation result 1 to 7), MO1 to 7(General-purpose output 1 to 7), EMFC(Emergency force drive
indicator),EMBP(Bypass mode indicator), WFT(Trace waiting signal), TRA(Trace running signal), LBK(Low battery of
keypad)(Valid when using option VOP), OVS(Overvoltage power Supply), AC0 to 3( Alarm code bit-0 to 3), SSE( PID soft start
error)
Relay/
Alarm relay
(1c) function
Output terminal
monitor *8)
The data of the monitor can be selected by the parameter of the output.
EMC filter can be enable (The filter exchange method can alter depending on the model)
-10 to 40°C(SH1-03410-H(SH1-1600H)toSH1-06600-H(SH1-3150H))only support ND(normal duty)andLD(low duty).
20 to 90%RH(No condensation allowed)
5.9m/s
2
(0.6G), 10 to 55Hz
SH1-00041-H(SH1-007H) to SH1-00620-H( SH1-220H)
2.94m/s
2
(0.3G), 10 to 55Hz
SH1-00770-H(SH1-300H) to SH1-06600-H(SH1-3150H)
1000 altitude or lower (location free from corrosive gas, oil mist, and dust)
The design life of the electrolytic capacitor on the board and the main circuit smoothing capacitor is 10 years.
The design life of the cooling fan is 10 years (models with cooling fan). But no dust.
Non-volatile memory parts on control circuit board.
CE marking
CE certification models are SH1-00041-H(SH1-007H) to SH1-03160-H(SH1-1320H).
Black (SH1-03410-H(SH1-1600H) and above models are unpainted (but front cover and terminal block cover are black))
・Communication option : Ethernet(Modbus-TCP)(P1-EN), EtherCAT® (P1-ECT), PROFINET® (P1-PN),
PROFIBUS® (P1-PB), CC-Link® (P1-CCL), DeviceNet® (P1-DN)
・Encoder Feedback option (Line driver input(RS422))(P1-FB)
・Analog input/output option (P1-AG)
Other optional
components
Braking resistor, AC reactor, DC reactor, noise filter,operator cable, harmonics suppresion unit, LCRfilter, analog panel,
regenerative braking unit, power regeneration converter, SJ300/SJ700 compatible screw type control terminal block
option(P1-TM2), PC software ProdriveNext.
*7) The threshold for signal output varies depending on the motor to be combined with the inverter, parameter adjustment, etc.
*8) The analog voltage and analog current monitor are estimated outputs of the analog meter connection. Maximum output value might deviate
slightly from 10V or 20mA by variation of the analog output circuit. If you want to change the characteristics, adjust the Ao1 and Ao2 adjustment
functions.There are some monitor data that cannot be output.
*9) In order to enable the EMC filter, connect to the neutral grounding supply. Otherwise, the leakage current may increase.
*10) Storage temperature is the temperature during transport.
*11) In accordance with the test methods of JIS C 60068-2-6:2010(IEC 60068-2-6:2007).
*12) In case of utilization at an altitude of 1000m or more, take into account that the atmospheric pressure is reduced by 1% for every 100m up. Apply
1% derating from the rated current by increasing every 100m, and conduct an evaluation test.
When using above 2500m ambient, please contact Hitachi Inverter distributer.
*13) Insulation distance is in accordance with CE standards.
*14) Use the 400V class inverter at an input voltage of 500VAC or below. If input voltage exceeds 500VAC due to fluctuation of power, use the inverter
at 40°C or lower ambient temperature.
*15) Modbus® is a registered trademark of Schneider Automation Inc.
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
PROFIBUS® and PROFINET® is registered trademark of PROFIBUS Nutzerorganisation e.V. (PNO).
CC-Link® is trade names of Mitsubishi Electric Co. DeviceNet® is the trademark of Open DeviceNet Vendor Association, Inc.