2-3
Chapter 2
Installation and Wiring
Installation environment
Avoid installing the inverter in a place where the
inverter is subject to dust, corrosive gases,
explosive gases, flammable gases, grinding fluid
mist, or salt water.
Foreign particles entering the inverter will cause of
failure. If you use the inverter in a considerably
dusty environment, install the inverter inside a
totally enclosure.
Installation method and position
Install the inverter vertically and securely with
screws or bolts on a surface that is free from
vibrations and that can bear the inverter weight.
If the inverter is not installed properly, its cooling
performance may be degraded and tripping or
inverter damage may result.
Mounting in an enclosure
When mounting multiple inverters in an enclosure
with a ventilation fan, carefully design the layout
of the ventilation fan, air intake port, and inverters.
An inappropriate layout will reduce the
inverter-cooling effect and raise the ambient
temperature. Plan the layout properly so that the
inverter ambient temperature will remain within
the range specified in the specification table.
When the inverter is installed below ventilation fan,
the incoming dust may adhere to the inverter. Place in
a position to avoid this falling dust.
Reduction of enclosure size
External heat sink installation may reduce internal
heat emission and reduce the enclosure size.
External heat sink mounting for the inverter
SH1-00041-HSH1-00126-H(SH1-007HSH1-037H)
requires an optional metal fitting.
Models other than the above can be mounted
using the brackets attached on the inverter. When
mounting the inverter with the heatsink outside
the enclosure, cut the mounting surface
depending on the panel cut dimensions.
The cooling section (including the heat sink)
positioned outside the enclosure has a cooling fan.
Therefore, do not place the enclosure in any
environment where it is exposed to water drops,
oil mist, or dust.
The heat sink part reaches a high temperature.
Install a protection cover as needed.
Watt loss (W) (at 100% load, approximate)
*400V class
SH1-*****-H
00041
00054
00083
00126
00175
00250
00310
00400
SH1-***H
007
015
022
037
055
075
110
150
Watt
loss
(W)
ND
62
94
96
145
235
240
260
361
LD
67
98
107
163
260
280
306
444
VLD
76
104
134
189
290
306
380
482
SH1-*****-H
00470
00620
00770
00930
01160
01470
01760
02130
SH1-***H
185
220
300
370
450
550
750
900
Watt
loss
(W)
ND
495
687
783
812
1047
1130
1570
2034
LD
601
805
854
880
1218
1488
1811
2150
VLD
633
860
920
971
1300
1592
2020
2359
SH1-*****-H
02520
03160
03410
03950
04460
04810
05500
06600
SH1-***H
1100
1320
1600
1850
2000
2200
2500
3150
Watt
loss
(W)
ND
2219
3872
3896
4091
4514
4710
5750
7545
LD
2397
4352
4379
4598
4622
5251
6250
7875
VLD
2557
4598
(Note: These data are reference values of our site and vary
depending on the power supply environment and the
motor power factor.)
(Unacceptable)
Ventilation
fan
Inverter
(Acceptable)
Ventilation
fan
Inverter
Position of ventilation fan
Screw
clamp
Screw
clamp
Screw
clamp
Screw
clamp