EasyManua.ls Logo

Hitachi SH1-900H - Page 86

Hitachi SH1-900H
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-43
Chapter 4
For parameter configuration
[HA210] to [HA234]
2nd motor When Intelligent Input terminal 024[SET] is enabled.
Code/Name
Range
(unit)
Initial
value
HA210 Stabilization constant, 2nd-motor
Same as HA110
HA112 Stabilization ramp function end
ratio, 2nd-motor
Same as HA112
HA113 Stabilization ramp function start
ratio, 2nd-motor
Same as HA113
HA215 Speed response, 2nd-motor
Same as HA115
HA220 ASR gain switching mode selection,
2nd-motor
Same as HA120
HA221 ASR gain switching time setting,
2nd-motor
Same as HA121
HA222 ASR gain mapping intermediate
speed 1, 2nd-motor
Same as HA122
HA223 ASR gain mapping intermediate
speed 2, 2nd-motor
Same as HA123
HA224 ASR gain mapping maximum speed,
2nd-motor
Same as HA124
HA225 ASR gain mapping P-gain 1,
2nd-motor
Same as HA125
HA226 ASR gain mapping I-gain 1,
2nd-motor
Same as HA126
HA227 ASR gain mapping P control P-gain 1,
2nd-motor
Same as HA127
HA228 ASR gain mapping P-gain 2,
2nd-motor
Same as HA128
HA229 ASR gain mapping I-gain 2,
2nd-motor
Same as HA129
HA230 ASR gain mapping P control P-gain 2,
2nd-motor
Same as HA130
HA231 ASR gain mapping P-gain 3,
2nd-motor
Same as HA131
HA232 ASR gain mapping I-gain 3,
2nd-motor
Same as HA132
HA233 ASR gain mapping P-gain 4,
2nd-motor
Same as HA133
HA234 ASR gain mapping I-gain 4,
2nd-motor
Same as HA134
[Hb102] to [Hb108]
Basic parameters for Induction motor
Code/Name
Range (unit)
Initial value
Hb102 Async.
Motor capacity
setting, 1st-motor
0.01 to
160.00 (kW)
(0.01 to
500.00(kW)
Motor capacity setting
(For the SH1-1600H or above
models, the maximum
setting range is 500.00
(kW). )
Hb103 Async.
Motor number of
poles setting,
1st-motor
0 to 23
( 2 poles to
48 poles )
1 (4 Poles)
Hb104 Async.
Motor base
frequency setting,
1st-motor
10.00 to
[Hb105] (Hz)
60.00(JPN)(USA)/
50.00(EU)(ASIA)(CHN)
Hb105 Async.
Motor maximum
frequency setting,
1st-motor
[Hb104] to
590.00 (Hz)
60.00(JPN)(USA)/
50.00(EU)(ASIA)(CHN)
Hb106 Async.
Motor rated
voltage, 1st-motor
1 to 1000 (V)
(400V Class)
400(JPN)(EU)(ASIA)(CHN)
460(USA)
Hb108 Async.
Motor rated
current, 1st-motor
0.01 to
10000.00 (A)
Motor capacity setting
If the motor capacity [Hb102] and number of poles
[Hb103] are changed, the motor characteristics are set
according to the internal Hitachi table values.
The output is decided by setting the frequency and
voltage. Below there is an example of V/f control.
By setting the motor rated current, a reference current
for the motor protection is set.
Initial value depends on the inverter.
Motor typical data
Code
Range of values (Unit)
Capacity
[Hb102]
0.01 to 160.00 (kW)
(0.01 to 500(kW)
for SH1-1600H or above models)
Number of poles
[Hb103]
0 to 23 (2 poles to 48 poles)
Frequency
[Hb104]
10.00 to 590.00 (Hz)
[Hb105]
10.00 to 590.00 (Hz)
Voltage
[Hb106]
1 to 1000 (V)
Current
[Hb108]
0.01 to 10000.00 (A)
Output
voltage
Motor rated
voltage
(Ex.) 400V
Command
frequency (Hz)
Base frequency
(Eg.)60Hz
Maximum
frequency

Related product manuals