4-47
Chapter 4
For parameter configuration
[Hd102] to [Hd118]
Permanent Magnet Sync. Motor(SM/PMM)
basic parameters
Code/Name
Range (unit)
Initial value
Hd102 Sync.
Motor capacity
setting, 1st-motor
0.01 to
160.00(kW)
(0.01 to
500.00(kW)
Factory setting
(The maximum value of the
setting range is 500.00
(kW) for SH1-1600H or above
models.)
Hd103 Sync.
Motor number of
poles setting,
1st-motor
0 to 23
(2 poles to
48 Poles)
Factory setting
Hd104 Sync.
Motor Base
frequency setting,
1st-motor
10.00 to
[Hd105](Hz)
Factory setting
Hd105 Sync.
Motor Maximum
frequency setting,
1st-motor
[Hd104] to
590.00(Hz)
Factory setting
Hd106 Sync.
Motor rated
voltage, 1st-motor
1 to 1000(V)
Factory setting
Hd108 Sync.
Motor rated
current, 1st-motor
0.01 to
10000.00 (A)
Factory setting
Code/Name
Range (unit)
Initial value
Hd110 Sync. Motor
constant R, 1st-motor
0.000001 to
1000.000000 (Ω)
Factory setting
Hd112 Sync. Motor
constant Ld, 1st-motor
0.000001 to
1000.000000 (mH)
Factory setting
Hd114 Sync. Motor
constant Lq, 1st-motor
0.000001 to
1000.000000 (mH)
Factory setting
Hd116 Sync. Motor
constant Ke, 1st-motor
0.1 to 100000.0
(mVs/rad)
Factory setting
Hd118 Sync. Motor
constant J, 1st-motor
0.00001 to
10000.00000 (kgm2)
Factory setting
The motor capacity and the number of poles will be set by
Hitachi characteristics table.
For SM/PMM, frequency, voltage, and the motor constants
setting are necessary.
If the maximum current of the motor is decided, Set the
Overcurrent detection level [bb160] with a margin.
Motor typical data
Code
Range of values (unit)
Capacity
[Hd102]
0.01 to 160.00 (kW)
(0.01 to 500.00(kW)
for SH1-1600H or above models)
Number of poles
[Hd103]
0 to 23 (2 poles to 48 Poles)
Frequency
[Hd104]
10.00 to 590.00 (Hz)
[Hd105]
10.00 to 590.00 (Hz)
Voltage
[Hd106]
1 to 1000 (V)
Current
[Hd108]
0.01 to 10000.00 (A)
Initial value depends on the inverter.
If motor capacity [Hd102], number of poles [Hd103] are
changed, the motor characteristics are set according to the
internal Hitachi table values.
The values of [Hd110] to [Hd114] can be acquired by no
rotation auto-tuning.
[Hd130] to [Hd-58]
Minimum frequency settings
Code/Name
Range (unit)
Initial
value
Hd130 Minimum frequency
adjustment for Sync.M, 1st-motor
0 to 50(%)
8
Hd131 No-Load current for
Sync.M, 1st-motor
0 to 100(%)
10
The synchronous control is switched to sensorless vector
control when the frequency reference is the base
frequency[Hd104] × [Hd130].
By [Hd131], the sensorless vector control no-load current is
set.
Magnetic pole position estimation SM(PMM)
Code/Name
Range (unit)
Initial
value
Hd132 Starting method for
Sync.M, 1st-motor
00(Synchronous)/
01(Initial motor
position estimate
(IMPE))
00
Hd133 IMPE 0V wait number for
Sync.M, 1st-motor
0 to 255
10
Hd134 IMPE detect wait
number for Sync.M, 1st-motor
0 to 255
10
Hd135 IMPE detect number for
Sync.M, 1st-motor
0 to 255
30
Hd136 IMPE voltage gain for
Sync.M, 1st-motor
0 to 200(%)
100
Hd137 IMPE Mg-pole position
offset, 1st-motor
0 to 359(deg)
0
For SM/PMM, if initial motor position estimate is enabled by
[Hd132], the inverter drives after magnetic pole position
estimation. If a slight reverse rotation occurs at startup after
the magnetic pole position estimation operation, set the start
position offset in the operation direction to [Hd137].
IVMS setting
Code/
Range(unit)
Initial
Value
Hd-41 IVMS carrier frequency
0.5 to 16.0(kHz)
2.0
Hd-42 Filter gain of IVMS current
detection
0 to 1000
100
Hd-43 Open-phase voltage
detection gain
00/01/02/03
00
Hd-44 Open-phase switching
threshold compensation
00(Disable)/
01(Enable)
01
Hd-45 SM(PMM)-IVMS speed
control P gain
0 to 1000
100
Hd-46 SM(PMM)-IVMS speed
control I gain
0 to 10000
100
Hd-47 SM(PMM)-IVMS wait time for
open-phase switching
0 to 1000
15
Hd-48 SM(PMM)-IVMS restriction
on the rotation-direction
determination
00(Disable)/
01(Enable)
01
Hd-49 SM(PMM)-IVMS open-phase
voltage detection timing adjustment,
0 to 1000
10
Hd-50 SM(PMM)-IVMS minimum
pulse width adjustment,
0 to 1000
100
Hd-51 IVMS threshold current limit
0 to 255(%)
100
Hd-52 IVMS threshold gain
0 to 255(%)
100
Hd-58 IVMS carrier-frequency
switching start/finish point *1)
0 to 50(%)
5
*1) Depends on the base frequency.
For more information, please contact your supplier or
local Hitachi inverter sales office.