PARAMETER LISTS FOR SJ700/L700
D-Monitoring functions:
D001 3001 3002 Output frequency X1000 RO Addr:0x0400 Sz: 4 Range:[0-400000]
D002 3003 3004 Output current X10 RO Addr:0x042C Sz: 2 Range:[0-10000]
D003 3005 3006 Direction of present running X1 RO Addr:0x044A Sz: 1 Range:[0-2]
D004 3007 3008 Feedback data of PID control X100 RO Addr:0x0404 Sz: 4 Range:[0-999900]
D005 3009 3010 Status of Input terminal X1 RO Addr:0x042E Sz: 2 Range:[0-65535]
D006 3011 3012 Status of output terminal X1 RO Addr:0x0446 Sz: 2 Range:[0-65535]
D007 3013 3014 Value of conversion of frequency X1000 RO Addr:0x0408 Sz: 4 Range:[0-39960000]
D008 3015 3016 Encoder detected frequency monitor (V2 mode only) X100 RO Addr:0x4100 Sz: 4 Range:[-40000-40000]
D009 3017 3018 Torque set monitor X1 RO Addr:0x410E Sz: 2 Range:[0-200]
D010 3019 3020 Torque bias monitor X1 RO Addr:0x4110 Sz: 2 Range:[-150-150]
D012 3023 3024 Output Torque X1 RO Addr:0x0430 Sz: 2 Range:[-300-300]
D013 3025 3026 Output voltage X10 RO Addr:0x0448 Sz: 2 Range:[0-10000]
D014 3027 3028 Input electric power X10 RO Addr:0x0432 Sz: 2 Range:[0-10000]
D015 3029 3030 Cumulative power monitor X1 RO Addr:0x40FC Sz: 4 Range:[0-9999999]
D016 3031 3032 Accumulated time during running X1 RO Addr:0x0344 Sz: 4 Range:[0-4294836225]
D017 3033 3034 Accumulated time during Power ON X1 RO Addr:0x0348 Sz: 4 Range:[0-4294836225]
D018 3035 3036 Fin temperature monitor X10 RO Addr:0x4112 Sz: 2 Range:[-200-2000]
D019 3037 3038 Motor temperature monitor (External thermistor) X10 RO Addr:0x4114 Sz: 2 Range:[-200-2000]
D022 3043 3044 Life expectancy warning monitor X1 RO Addr:0x411D Sz: 1 Range:[0-3]
D023 3045 3046 Program counter (EZ-sequence program) X1 RO Addr:0x4116 Sz: 2 Range:[0-1023]
D024 3047 3048 Program number (EZ-sequence program) X1 RO Addr:0x4118 Sz: 2 Range:[0-9999]
D025 3049 3050 User monitor 1(EZ-sequence function) X1 RO Addr:0x4120 Sz: 4 Range:[-2147483647-2147483647]
D026 3051 3052 User monitor 2(EZ-sequence function) X1 RO Addr:0x4124 Sz: 4 Range:[-2147483647-2147483647]
D027 3053 3054 User monitor 3(EZ-sequence function) X1 RO Addr:0x4128 Sz: 4 Range:[-2147483647-2147483647]
D028 3055 3056 Pulse counter(input function) X1 RO Addr:0x412C Sz: 4 Range:[0-2147483647]
D029 3057 3058 Position set monitor X1 RO Addr:0x4130 Sz: 4 Range:[-1073741820-1073741820]
D030 3059 3060 Position monitor X1 RO Addr:0x4134 Sz: 4 Range:[-1073741820-1073741820]
D078 3155 3156 Pointer of history of last trip(error) X1 RO Addr:0x0363 Sz: 1 Range:[0-5]
D080 3159 3160 Accumulated number of Trip(error) X1 RO Addr:0x0360 Sz: 2 Range:[0-65535]
D081 3161 3162 Factor and Status of Trip1 X1 RO Addr:0x0364 Sz: 4 Range:[0-255]
D355 3709 3710 Frequency of Trip1 X100 RO Addr:0x0368 Sz: 4 Range:[0-40000]
D356 3711 3712 Output current of Trip1 X10 RO Addr:0x036C Sz: 2 Range:[0-10000]
D357 3713 3714 PN voltage (DC voltage) of Trip1 X10 RO Addr:0x036E Sz: 2 Range:[0-10000]
D358 3715 3716 Accumulated time during running of Trip1 X1 RO Addr:0x0370 Sz: 4 Range:[0-4294836225]
D359 3717 3718 Accumulated time during power ON of Trip1 X1 RO Addr:0x0374 Sz: 4 Range:[0-4294836225]
D082 3163 3164 Factor and Status of Trip2 X1 RO Addr:0x0378 Sz: 4 Range:[0-255]
D361 3721 3722 Frequency of Trip2 X100 RO Addr:0x037C Sz: 4 Range:[0-40000]
D362 3723 3724 Output current of Trip2 X10 RO Addr:0x0380 Sz: 2 Range:[0-10000]
D363 3725 3726 PN voltage (DC voltage) of Trip2 X10 RO Addr:0x0382 Sz: 2 Range:[0-10000]
D364 3727 3728 Accumulated time during running of Trip2 X1 RO Addr:0x0384 Sz: 4 Range:[0-4294836225]
D365 3729 3730 Accumulated time during power ON of Trip2 X1 RO Addr:0x0388 Sz: 4 Range:[0-4294836225]
D083 3165 3166 Factor and Status of Trip3 X1 RO Addr:0x038C Sz: 4 Range:[0-255]
D367 3733 3734 Frequency of Trip3 X100 RO Addr:0x0390 Sz: 4 Range:[0-40000]
D368 3735 3736 Output current of Trip3 X10 RO Addr:0x0394 Sz: 2 Range:[0-10000]
D369 3737 3738 PN voltage (DC voltage) of Trip3 X10 RO Addr:0x0396 Sz: 2 Range:[0-10000]
D370 3739 3740 Accumulated time during running of Trip3 X1 RO Addr:0x0398 Sz: 4 Range:[0-4294836225]
D371 3741 3742 Accumulated time during power ON of Trip3 X1 RO Addr:0x039C Sz: 4 Range:[0-4294836225]
D084 3167 3168 Factor and Status of Trip4 X1 RO Addr:0x03A0 Sz: 4 Range:[0-255]
D373 3745 3746 Frequency of Trip4 X100 RO Addr:0x03A4 Sz: 4 Range:[0-40000]
D374 3747 3748 Output current of Trip4 X10 RO Addr:0x03A8 Sz: 2 Range:[0-10000]
D375 3749 3750 PN voltage (DC voltage) of Trip4 X10 RO Addr:0x03AA Sz: 2 Range:[0-10000]
D376 3751 3752 Accumulated time during running of Trip4 X1 RO Addr:0x03AC Sz: 4 Range:[0-4294836225]
D377 3753 3754 Accumulated time during power ON of Trip4 X1 RO Addr:0x03B0 Sz: 4 Range:[0-4294836225]
D085 3169 3170 Factor and Status of Trip5 X1 RO Addr:0x03B4 Sz: 4 Range:[0-255]
D379 3757 3758 Frequency of Trip5 X100 RO Addr:0x03B8 Sz: 4 Range:[0-40000]
D380 3759 3760 Output current of Trip5 X10 RO Addr:0x03BC Sz: 2 Range:[0-10000]
D381 3761 3762 PN voltage (DC voltage) of Trip5 X10 RO Addr:0x03BE Sz: 2 Range:[0-10000]
D382 3763 3764 Accumulated time during running of Trip5 X1 RO Addr:0x03C0 Sz: 4 Range:[0-4294836225]
D383 3765 3766 Accumulated time during power ON of Trip5 X1 RO Addr:0x03C4 Sz: 4 Range:[0-4294836225]
D086 3171 3172 Factor and Status of Trip6 X1 RO Addr:0x03C8 Sz: 4 Range:[0-255]
D385 3769 3770 Frequency of Trip6 X100 RO Addr:0x03CC Sz: 4 Range:[0-40000]
D386 3771 3772 Output current of Trip6 X10 RO Addr:0x03D0 Sz: 2 Range:[0-10000]
D387 3773 3774 PN voltage (DC voltage) of Trip6 X10 RO Addr:0x03D2 Sz: 2 Range:[0-10000]
D388 3775 3776 Accumulated time during running of Trip6 X1 RO Addr:0x03D4 Sz: 4 Range:[0-4294836225]
D389 3777 3778 Accumulated time during power ON of Trip6 X1 RO Addr:0x03D8 Sz: 4 Range:[0-4294836225]
D101 3201 3202 Output frequency after Vector control X1000 RO Addr:0x040C Sz: 4 Range:[0-400000]
D102 3203 3204 DC Voltage , X10 RO Addr:0x043C Sz: 2 Range:[0-10000]
D103 3205 3206 On time of BRD running X10 RO Addr:0x043E Sz: 2 Range:[0-1000]
D104 3207 3208 Used rate of electronics thermal protection X10 RO Addr:0x0440 Sz: 2 Range:[0-1000]
D106 3211 3212 MCU Version X1 RO Addr:0x0438 Sz: 2 Range:[0-65535]
D109 3217 3218 Maximum DC bus voltage monitor X10 RO Addr:0x410C Sz: 2 Range:[0-9999]
D110 3219 3220 Temperature monitor (on board thermistor) X10 RO Addr:0x4138 Sz: 2 Range:[-200-2000]
D111 3221 3222 Maximum temperature monitor (on board thermistor) X10 RO Addr:0x413A Sz: 2 Range:[-200-2000]
F-Basic profile functions:
F001 4001 4002 Set frequency(Hz) / PID Setpoint (%) X1000 RO Addr:0x0420 Sz: 4 Range:[0-400000]
F002 4003 4004 1st Acceleration time 1 X100 RME R/W Addr:0x0058 Sz: 4 Range:[1-360000]
F202 4403 4404 2nd Acceleration time 1 X100 RME R/W Addr:0x005C Sz: 4 Range:[1-360000]
F302 4603 4604 3rd Acceleration time 1 X100 RME R/W Addr:0x0060 Sz: 4 Range:[1-360000]
F003 4005 4006 1st Deceleration time 1 X100 RME R/W Addr:0x0064 Sz: 4 Range:[1-360000]
F203 4405 4406 2nd Deceleration time 1 X100 RME R/W Addr:0x0068 Sz: 4 Range:[1-360000]
F303 4605 4606 3rd Deceleration time 1 X100 RME R/W Addr:0x006C Sz: 4 Range:[1-360000]
F004 4007 4008 Selection of running direction for DIG-OPE X1 R/W Addr:0x023E Sz: 1 Range:[0-1]
A-Standard functions:
A001 0001 0002 Selection of frequency command destination X1 R/W Addr:0x023F Sz: 1 Range:[0-5]
A002 0003 0004 Selection of running command destination X1 R/W Addr:0x0240 Sz: 1 Range:[1-5]
A003 0005 0006 1st Base frequency X1 R/W Addr:0x00F0 Sz: 2 Range:[30-400]