State Controller FMD drive trays
Operating 50°F to 104°F
(10°C to 40°C)
DKC-F810I-1R6FN/3R2FN/6R4FN/7R0FP/14RFP
drive is installed: 50°F to 104°F (10°C to 40°C)
Non-operating 14°F to 122°F
(-10°C to 50°C)
14°F to 95°F (-10°C to 35°C)
Transport,
storage
-22°F to 140°F
(-30°C to 60°C)
-22°F to 122°F (-30°C to 50°C)
Temperature
change rate
(°C/h)
10 or less
Humidity
State Percentage
Operating 8 to 80
Non-operating 8 to 90
Transport, storage (%) 5 to 95
Maximum wet bulb temperature (°C) 29 (non-condensing)
Vibration
State m/s
2
Operating 2.5 or less
Within 5 seconds (resonance point: 10 Hz or
less)
Non-operating 5.0 or less at 5 Hz to 300 Hz (no damage to
product)
9.8 (1.0 G)
Within 5 seconds (resonance point: 10 Hz or
less)
Transport (packed) 5.0 or less
Environmental specifications
Appendix C: Environmental specifications for VSP N800