Refrigerant Piping Connection
enter the unit. The presence of other gases or substances will lower the unit’s capacity and can cause
abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.
Note on Pipe Length
vibration & excessive noise.
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
MODEL
MAX. LENGTH
MAX. DROP HEIGHT
R410A,R32 Inverter
Split Air Conditioner
82" (25 m)
33" (10 m)
98.5" (30 m) 66" (20 m)
164" (50 m) 82" (25 m)
Step 1: Cut the pipes.
When preparing refrigerant pipes, take extra care
future maintenance.
1. Measure the distance between the indoor and
outdoor units.
2. Use a pipe cutter to cut the pipe a little longer
than the measured distance.
3. Make sure that the pipe is cut at a perfect
90° angle.
DO NOT DEFORM THE PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform
the pipe while cutting. This will drastically reduce
Step 2: Remove the burrs.
Burrs can affect the airtight seal of the refrigerant
piping connection. They must be completely
removed.
1. Hold the pipe at a downward angle to
prevent the burrs from falling into the pipe.
2. Use a reamer or deburring tool to remove all
the burrs from the cut section of the pipe.
Pipe
Reamer
Point Down
Step 3: Flare the pipe ends.
seal.
1. After removing the burrs from the cut pipe,
seal the ends with PVC tape to prevent
foreign materials from entering the pipe.
2. Sheath the pipe with insulating material.
Oblique Rough Warped
90°