Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
Fault Finding:
Set-up Unit does not reach the first
screen.
• If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
• There may be a controller with the same
name, already logged on the network.
• There may be a maximum 32 controllers
already on the network segment.
• Check on the InTouch panel, P.C. or
Parameter DIN Range/Units Default
Setting
Dsg
n.
Act.
Red Cycle Temperature 0 1 to 7 / °C 4
Red OT Alarm Temp. 2 7 to 10 / °C 8
Red UT Alarm Temp. 1 -3 to 4 / °C 2
Defrost Type:0=Elect.;1=Off Cyc. 3 0 to 1 0
Yellow Cycle Temperature 4 -1 to 4 / °C 1
Yellow OT Alarm Temp. 6 4 to 7 / °C 5
Yellow UT Alarm Temp. 5 -6 to 1 / °C -1
Defrost Type:0=Elect.;1=Off Cyc. 7 0 to 1 0
White Cycle Temperature 8 4 to 12 / °C 8
White OT Alarm Temp. 10 11 to 14 / °C 12
White UT Alarm Temp. 9 1 to 6 / °C 4
Defrost Type:0=Elect.;1=Off Cyc. 11 0 to 1 1
Red Log OT Alarm 20 8 to 10 / °C 8
Red Log UT Alarm 19 -1 to 4 / °C 2
Yellow Log OT Alarm 22 5 to 7 / °C 5
Yellow Log UT Alarm 21 -2 to 1 / °C 0
White Log OT Alarm 24 12 to 14 / °C 12
White Log UT Alarm 23 3 to 7 / °C 4
Lead Cyc. Diff 12 0 to 30 / °C 1.5
Lag. Cut In 13 0 to 3 / °C 1
Lag Cut Out 14 0 to 3 / °C 1
Case Type: 0=Red ; 1=Yellow ;
2=White
16 0 to 2 0
Control Weight 15 0 to 100 / % 50
Display Weight 16 0 to 100 / % 50
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod./Alarm
18 0 to 3 0
Off Cycle Defrost Max.Temp. 30 -49 to 60 / °C 10
Off Cycle Defrost Minimum Time 28 00:00 to 99:00/Min:Sec 05:00
Off Cycle Defrost Maximum Time 29 00:00 to 99:00/Min:Sec 24:00
Electric Defrost Max. Temp. 33 -49 to 60 / °C 10
Electric Defrost Minimum Time 31 00:00 to 99:00/Min:Sec 05:00
Electric Defrost Maximum Time 32 00:00 to 99:00/Min:Sec 24:00
Defrost Start 26 00:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 27 0 to 6 6
No Defrost Time 41 0 to 25/ Hrs. 7
Alarm Delay Fixed / Min:Sec 05:00
Drain Down Time 34 00:00 to 03:00/Min:Sec 01:30
Defrost Min. Recovery Time 35 00:00 to 35:00/Min:Sec 20:00
Defrost Max. Recovery Time 36 15:00 to 35:00/Min:Sec 30:00
Defrost Alarm Temp. 37 -49 to 60 / °C 20
Defrost Mode: 0=Local ;
1=Remote
38 0 to 1 0
Defrost Hold: 0=Off ; 1=On 40 0 to 1 0
Pulse Defrost: 0=Off ; 1=On 39 0 to 1 0
Hour 42 0 to 23
Minute 43 0 to 59
Day 44 0 to 31
Month 45 0 to 12
Year 46 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
47 0 to 2 0
Lights/Blind: 0=Local ; 1=Remote
; 2=Man.Off ; 3=Man.On
48 0 to 3 0
Polarity: 0=N/O ; 1=N/C 49 0 to 1 0
Latch Alarm: 0=Off ; 1=On 25 0 to 1 0
Sunday (Blinds) Up / Down 50/51 00:00 to 23:59/Hrs:Mins 08:00/20:00
Monday (Blinds) Up / Down 52/53 00:00 to 23:59/Hrs:Mins 08:00/20:00
Tuesday (Blinds) Up / Down 54/55 00:00 to 23:59/Hrs:Mins 08:00/20:00
Wednesday (Blinds) Up / Down 56/57 00:00 to 23:59/Hrs:Mins 08:00/20:00
Thursday (Blinds) Up / Down 58/59 00:00 to 23:59/Hrs:Mins 08:00/20:00
Friday (Blinds) Up / Down 60/61 00:00 to 23:59/Hrs:Mins 08:00/20:00
Saturday (Blinds) Up / Down 62/63 00:00 to 23:59/Hrs:Mins 08:00/20:00
Gas Alarm: 0=Off ; 1=On 64 0 to 1 0
Minor Leak 65 0 to 3500 / ppm. 50
Major Leak 66 0 to 3500 / ppm. 200
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0