Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
There may be a controller with the same
name, already logged on the network.
There may be a maximum 32 controllers
already on the network segment.
Check on the InTouch panel, P.C. or
Supervisor.
Parameter DIN Range/Units Default
HT(LT)
Dsgn Act.
Cut in Temperature 0 -49 to 30 / °C 0 (-20)
Differential Below 1 0 to 30 / °C 1.5 (2)
Control Weight 2 0 to 100 / % 50
Display Weight 3 0 to 100 / % 50
Section 1: OT Alarm 44 -49 to 60 / °C 5 (-16)
Section 1: UT Alarm 45 -49 to 60 / °C -2 (-25)
Section 2: OT Alarm 47 -49 to 60 / °C 5 (-16)
Section 2: UT Alarm 48 -49 to 60 / °C -2 (-25)
Section 3: OT Alarm 50 -49 to 60 / °C 5 (-16)
Section 3: UT Alarm 51 -49 to 60 / °C -2 (-25)
Alarm Delay 17 00:00 to 99:00/Min:Sec 20:00
Latch Alarm: 0=Off ; 1=On 18 0 to 1 0
Defrost Start 4 00:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 5 0 to 6 6
No Defrost Time 6 0 to 25 / Hrs. 7
Section 1: Defrost Term. Temp. 46 -49 to 60 / °C 10
Section 2: Defrost Term. Temp. 49 -49 to 60 / °C 10
Section 3: Defrost Term. Temp. 52 -49 to 60 / °C 10
Defrost Minimum Time 7 00:00 to 99:00/Min:Sec 05:00
Defrost Maximum Time 8 00:00 to 99:00/Min:Sec 24:00
(25:00)
Defrost Min. Recovery Time 9 00:00 to 99:00/Min:Sec 20:00
Defrost Max. Recovery Time 10 00:00 to 99:00/Min:Sec 30:00
Drain Down Time 11 00:00 to 20:00/Min:Sec 01:30
Defrost Alarm Temp. 12 -49 to 60 / °C 20
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas
13 0 to 2 0
Defrost Mode: 0=Local ;
1=Remote
14 0 to 1 0
Defrost Hold: 0=Off ; 1=On 15 0 to 1 0
Pulse Defrost: 0=Off ; 1=On 16 0 to 1 0
Hour 19 0 to 23
Minute 20 0 to 59
Day 21 0 to 31
Month 22 0 to 12
Year 23 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
24 0 to 2 0
Lights/Blinds: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
25 0 to 3 0
Polarity: 0=N/O ; 1=N/C 26 0 to 1 0
Sunday (Blinds) Up / Down 27/28 00:00 to 23:59/Hrs:Mins 08:00/20:00
Monday Up / Down 29/30 00:00 to 23:59/Hrs:Mins 08:00/20:00
Tuesday Up / Down 31/32 00:00 to 23:59/Hrs:Mins 08:00/20:00
Wednesday Up / Down 33/34 00:00 to 23:59/Hrs:Mins 08:00/20:00
Thursday Up / Down 35/36 00:00 to 23:59/Hrs:Mins 08:00/20:00
Friday Up / Down 37/38 00:00 to 23:59/Hrs:Mins 08:00/20:00
Saturday Up / Down 39/40 00:00 to 23:59/Hrs:Mins 08:00/20:00
Gas Alarm: 0=Off ; 1=On 41 0 to 1 0
Minor Leak 42 0 to 3500 / ppm. 50
Major Leak 43 0 to 3500 / ppm. 200
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
LA Log probe alarm
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
E1 Plant fault 1
E2 Plant fault 2
ES Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Comments:
Universal Controller -
3 Section
ZA-10006-YAD
Issue a : 5/11/96