Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
There may be a controller with the same
name, already logged on the network.
There may be a maximum 32 controllers
already on the network segment.
Check on the InTouch panel, P.C. or
Supervisor.
Parameter DIN Range/Units Default
HT(LT)
Dsgn Act.
Cut in Temperature 0 -49 to 30 / °C 0 (-20)
Differential Below 1 0 to 30 / °C 1.5 (2)
Control Weight 2 0 to 100 / % 50
Display Weight 3 0 to 100 / % 50
Log Probe: 0=Off ; 1=Product ;
2=Alarm ; 3=Prod/Alm
8 0 to 3 0
OT Alarm 5 -49 to 60 / °C 5 (-16)
UT Alarm 4 -49 to 60 / °C -2 (-25)
Alarm Delay 6 00:00 to 99:00/Min:Sec 20:00
Defrost Start 11 00:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 12 0 to 6 6
No Defrost Time 27 0 to 25 / Hrs. 7
Log OT Alarm 10 -49 to 60 / °C 5 (-15)
Log UT Alarm 9 -49 to 60 / °C 0 (-25)
Latch Alarm: 0=Off ; 1=On 7 0 to 1 0
Gas Defrost Detect 13 0 to 30 / °C 18
Defrost Terminate Temperature 14 -49 to 30 / °C 10 (14)
Defrost Minimum Time 15 00:00 to 99:00/Min:Sec 05:00
Defrost Maximum Time 16 00:00 to 99:00/Min:Sec 24:00
(25:00)
Drain Down Time 17 00:00 to 20:00/Min:Sec 01:30
Defrost Min. Recovery Time 18 00:00 to 99:00/Min:Sec 20:00
Defrost Max. Recovery Time 19 00:00 to 99:00/Min:Sec 30:00
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas
22 0 to 2 0
Defrost Alarm Temp. 23 -49 to 60 / °C 20
Defrost Mode: 0=Local ;
1=Remote
24 0 to 1 0
Defrost Hold: 0=Off ; 1=On 26 0 to 1 0
Pulse Defrost: 0=Off ; 1=On 25 0 to 1 0
Pump Down 1 20 00:00 to 07:00/Min:Sec 00:00
Pump Down 2 21 00:00 to 07:00/Min:Sec 00:00
Hour 28 0 to 23
Minute 29 0 to 59
Day 30 0 to 31
Month 31 0 to 12
Year 32 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
33 0 to 2 0
Lights/Blinds: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
34 0 to 3 0
Polarity: 0=N/O ; 1=N/C 35 0 to 1 0
Sunday (Blinds) Up / Down 36/37 00:00 to 23:59/Hrs:Mins 08:00/20:00
Monday Up / Down 38/39 00:00 to 23:59/Hrs:Mins 08:00/20:00
Tuesday Up / Down 40/41 00:00 to 23:59/Hrs:Mins 08:00/20:00
Wednesday Up / Down 42/43 00:00 to 23:59/Hrs:Mins 08:00/20:00
Thursday Up / Down 44/45 00:00 to 23:59/Hrs:Mins 08:00/20:00
Friday Up / Down 46/47 00:00 to 23:59/Hrs:Mins 08:00/20:00
Saturday Up / Down 48/49 00:00 to 23:59/Hrs:Mins 08:00/20:00
Energy Saving: 0=Off ; 1=On 50 0 to 1 0
Entry Diff. 51 -49 to 60 / °C 4
Exit Diff. 52 -49 to 60 / °C 8
Exit Time 53 00:00 to 20:00/Min:Sec 00:30
Cycle Temp. 54 -49 to 60 / °C 5
Fan Diff. 55 0 to 60 / °C 4
Run on Time 56 00:00 to 20:00/Min:Sec 05:00
Def. Term. 57 -49 to 30 / °C 14
Gas Alarm: 0=Off ; 1=On 58 0 to 1 0
Minor Leak 59 0 to 3500 / ppm. 50
Major Leak 60 0 to 3500 / ppm. 200
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
LA Log probe alarm
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
E1 Plant fault 1
E2 Plant fault 2
ES Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Comments:
Universal Controller -
Generic
ZA-10002-YAD
Issue a : 5/11/96