Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
There may be a controller with the same
name, already logged on the network.
There may be a maximum 32 controllers
already on the network segment.
Check on the InTouch panel, P.C. or
Supervisor.
Parameter DIN Range/Units Default
HT(LT)
Dsgn. Act.
Red Cycle Temperature 0 1 to 7 (-49 to 60) / °C 4 (-22)
Red OT Alarm Temp. 2 7 to 10 (-49 to 60) / °C 8 (-15)
Red UT Alarm Temp. 1 -3 to 4 (-49 to 60) / °C 2 (-30)
Yellow Cycle Temperature 3 -1 to4 (-49 to 60) / °C 1 (-22)
Yellow OT Alarm Temp. 5 4 to 7 (-49 to 60) / °C 5 (-15)
Yellow UT Alarm Temp. 4 -6 to 1 (-49 to 60) / °C -1 (-30)
White Cycle Temperature 6 4 to 12 (-49 to 60) /°C 8 (-22)
White OT Alarm Temp. 8 11 to 14 (-49 to 60) / °C 12 (-15)
White UT Alarm Temp. 7 1 to 6 (-49 to 60) / °C 4 (-30)
Red Log OT Alarm 15 8 to 10 (-49 to 60) / °C 8(-15)
Red Log UT Alarm 14 -1 to 4 (-49 to 60) / °C 2(-25)
Yellow Log OT Alarm 17 5 to 7 (-49 to 60) / °C 5(-15)
Yellow Log UT Alarm 16 -2 to 1 (-49 to 60) / °C 0(-25)
White Log OT Alarm 19 12 to 14 (-49 to 60) / °C 12(-15)
White Log UT Alarm 18 3 to 7 (-49 to 60) / °C 4(-25)
Cycle Differential 10 0.5 to 4 / °C 1.5(2.0)
Case Type: 0=Red ; 1=Yellow ;
2=White
9 0 to 2 0
Alarm Delay Fixed / Min:Sec 05:00 (10:00)
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod./Alarm
13 0 to 3 0
Control Weight 11 0 to 100 / % 50
Display Weight 12 0 to 100 / % 50
Defrost Start 21 00:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 22 0 to 6 6
No Defrost Time 23 0 to 25 / Hrs. 7
Gas Defrost Detect 24 10 to 30 / °C 18.0
Defrost Minimum Time 26 00:00 to 05:00/Min:Sec 05:00
Defrost Maximum Time 27 00:00 to 26:00/Min:Sec 24:00 (25:00)
Defrost Terminate Temperature 25 6 to 14 / °C 10 (14)
Drain Down Time 28 00:00 to 03:00/Min:Sec 01:30
Defrost Min.Recovery Time 29 00:00 to 35:00/Min:Sec 20:00
Defrost Max.Recovery Time 30 15:00 to 35:00/Min:Sec 30:00
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas
35 0 to 2 0
Pump Down 1 31 00:00 to 07:00/Min:Sec 00:00
Pump Down 2 32 00:00 to 07:00/Min:Sec 00:00
Defrost Alarm Temp. 33 -49 to 60 / °C 20
Defrost Mode:0=Local;1=Remote 34 0 to 1 0
Defrost Hold: 0=Off ; 1=On 36 0 to 1 0
Pulse Defrost: 0=Off ; 1=On 37 0 to 1 0
Hour 38 0 to 23
Minute 39 0 to 59
Day 40 0 to 31
Month 41 0 to 12
Year 42 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
43 0 to 2 0
Lights/Blind: 0=Local ;1=Remote
; 2=Man.Off ; 3=Man.On
44 0 to 3 0
Polarity: 0=N/O ; 1=N/C 45 0 to 1 0
Alarm Latch: 0=Off ; 1=On 20 0 to 1 0
Sunday (Blinds) Up / Down 46/47 00:00 to 23:59/Hrs:Mins 08:00/20:00
Monday (Blinds) Up / Down 48/49 00:00 to 23:59/Hrs:Mins 08:00/20:00
Tuesday (Blinds) Up / Down 50/51 00:00 to 23:59/Hrs:Mins 08:00/20:00
Wednesday (Blinds) Up / Down 52/53 00:00 to 23:59/Hrs:Mins 08:00/20:00
Thursday (Blinds) Up / Down 54/55 00:00 to 23:59/Hrs:Mins 08:00/20:00
Friday (Blinds) Up / Down 56/57 00:00 to 23:59/Hrs:Mins 08:00/20:00
Saturday (Blinds) Up / Down 58/59 00:00 to 23:59/Hrs:Mins 08:00/20:00
Energy Saving: 0=Off ; 1=On 60 0 to 1 0
Entry Diff. 61 -49 to 60 / °C 4
Exit Diff. 62 -49 to 60 / °C 8
Exit Tme 63 00:00 to 20:00/Min:Sec 00:30
Cycle Temp. 64 -49 to 60 / °C 5
Fan Diff. 65 0 to 60 / °C 4
Run on Time 66 00:00 to 20:00/Min:Sec 05:00
Def. Term. 67 -49 to 30 / °C 14
Gas Alarm: 0=Off ; 1=On 68 0 to 1 0
Minor Leak 69 0 to 3500 / ppm. 50
Major Leak 70 0 to 3500 / ppm. 200
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
YAD08y / 65EAEE
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
LA Log probe alarm
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
E1 Plant fault 1
E2 Plant fault 2
ES Energy-Saving Mode
Store:............................................
Controller
Name:
Designer:.....................................
Date:............................................
Engineer:......................................
Date:.............................................
Comments:
Universal Controller -
3 Range
ZA-10004-YAD
Issue a : 5/11/96