Chapter 10 Program Example
41 Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB Users Guide R220
Honeywell January 2019
10.4 Example of communication with 2MLL-PMEB (P2P)
This example shows a program that is installed on No. 0 slot of ML200 No. 0 base, slave module
should offer the DPv1 service. Pnet I/F module reads 10 bytes data of 0x04 slot 0x15 index from
slave module and saves to %MW100 of PLC. Pnet I/F module writes 10 bytes data to 0x04 slot 0x15
index of slave module.
P2P function
Condition
flag
Data type
No. of variable
Destination
station
2MLL-
PMEB
(Master)
Slave
READ
%MX0
BYTE
1
2
Slave
WRITE
%MX1
BYTE
1
2
[Table 10.4.1] P2P I/O Structure and Sending/Receiving Data
10.4.1 SoftMaster settings
This part describes how to assign the internal memory by SoftMaster..
Click ‘Project’ ->’New Project’ and select project name and PLC series in the New Project window.