Installation and Operations Guide
|
ACM-VLX/VLX/EXP/AXM
92
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
Properties of VLX/ACM-VLX File objects
Properties of VLX/ACM-VLX Notification Class objects
Table 34 Prope rtie s of VLX/ACM-VLX file objects
Prope rty W Type Example Re marks
archive Boole an FALS E Indicates whethe r the file has be e n s ave d for backup.
de s cription Characte r s tring VLX/ACM
ROC File
A de s cription as s igne d to de s cribe the obje ct’s function.
file -access-method Enume rate d stre am
access
file -s ize Unsigned 983040 The s ize of the file, in bytes .
file -type Characte r string ROC Als o DDC or TRAP.
modification-date Time 4/29/2021
10:22:20:00a
The date and time the file was las t modifie d.
obje ct-ide ntifie r BACne t_ Object_
Id e n tifie r
file 0 This prope rty cons ists of the obje ct-type prope rty and
the object ins tance , which is a nume ric code that
identifies the object of interest.
obje ct-name Character s tring File 0
obje ct-type Enumerated file
read-only Boole an TRUE Indicates whethe r the file can be writte n to by BACne t
services.
Table 35 Prope rtie s of VLX/ACM-VLX Notification Clas s obje cts
Prope rty W Type Example Re marks
ack-re quired
Bit s tring To offnormal
= 1, to fault =
1, to normal
= 1
Indicates whethe r an acknowledgme nt is re quired for
e ve nt transitions. A 1 indicate s that acknowledgme nt is
require d. S e t up at the ope rator workstation.
de s cription
Characte r string Alarm
Handle r
An e ditable de s cription of the obje ct’s location or
function.
notification-clas s Uns igne d 1 Echoe s the obje ct ins tance .
obje ct-ide ntifie r BACne t_ Object_
Id e n tifie r
Notific atio n
-c las s 1
This prope rty cons ists of the obje ct-type prope rty and the
obje ct instance , which is a nume ric code that ide ntifie s
the object of interest.
obje ct-name
Characte r string Alarm
Handle r 1
obje ct-type Enumerated Notification-
class
re c ip ie n t- lis t
Lis t <List of
BACne t
Destination>
Lis ts the de vice s that will re ce ive notification whe n the
notification clas s trans itions . S e t up at the ope rator
workstation.
priority
Array of Uns igne d Indicate s the priority to be used for event notifications for
TO-OFFNORMAL, TO-FAULT, and TO-NORMAL
e ve nts , re s pe ctive ly.