EasyManua.ls Logo

Honeywell ALERTON ACM-VLX - Properties of VLX;ACM-VLX Program Objects

Honeywell ALERTON ACM-VLX
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Operations Guide
|
Appendix F: BACnet object and property reference
© Honeywell. All Rights Reserved. LT-VLXEXPAXMIOG Rev. 01
93
Properties of VLX/ACM-VLX Program objects
Table 36 Properties of VLX/ACM-VLX Program objects
Prope rty W Type Example Re marks
de s cription Characte r s tring Occupied
Setpoint
A de s cription as s igne d to de s cribe the obje ct’s function.
de s cription-of-halt Characte r string Program
halte d by
request
ins tance-of Characte r string ale rton hq
alerVLX
0*00000000*
<</ACM-
VLX? >>
He ader information for the file . Program 0 does not
support this prope rty.
obje ct-ide ntifie r BACne t_ Object_
Id e n tifie r
program
1024
This prope rty cons ists of the obje ct-type prope rty and
the object ins tance , which is a nume ric code that
identifies the object of interest.
obje ct-name Characte r string Pro g ram
Objec t 1024
obje ct-type Enumerated Program
out-of-s e rvice Boole an FALS E
program-change
Enumerated READY Us e d to command the program s tate . A program can be
stopped using the HALT command, for example , and
starte d again with RESTART.
program-location Character string DDC
Seque nce =
60
Set when program s tops.
program-s tate Enume rate d RUNNING Possible state s include RUNNING, IDLE, HALTED.
reas on-for-halt Enumerate d PROGRAM
reliability Enumerated NO FAULT
DETECTED
status -flags Bit s tring In alarm = 0,
fault = 0,
ove rridden =
0, out of
se rvice = 0
A four-pos ition bit s tring that indicate s the status of the
obje ct. If a s tatus bit =1, that status is TRUE.

Related product manuals