C7007A, C7008A, C7009A FLAME ROD HOLDER & FLAME ROD ASSEMBLIES
5 60-2024—06
Protect the leadwire from excessive radiant or reflected heat. 
If any portion of the wire will be exposed to temperatures in 
excess of 125° F [51.6° C], a heat-resistant wire should be 
used (see Accessories). For wiring where temperatures do 
not exceed 125° F [52° C], wire with thermoplastic insulation 
may be used. If wire is enclosed in conduit, install a two foot 
flexible connection to the head of the unit. This permits easy 
removal of unit from combustion chamber.  
FLAME ROD REPLACEMENT
To replace flame rod in the C7008A: remove the cover, pull off 
the Rajah connector with the wiring, remove (unscrew) the 
terminal nut and the lock washer at the base of flame rod 
assembly to free the flame rod. Pull out the old flame rod and 
insert the new rod. Then replace the lock washer, screw on 
the terminal nut, push the wiring connector back on, and 
replace the cover.
Procedure is the same for C7009A except that there is no 
cover.
To replace flame rod in the C7007A: Remove the cover, 
loosen the flame rod setscrew, pull the flame rod out, insert 
the replacement rod, and tighten the setscrew. Replace the 
cover.  
A NOTE ON OIL BURNER USAGE
If the flame rod is used to prove a gas pilot on an oil 
installation, oil or soot deposits must not be allowed to form on 
flame rod insulator. Such deposits might form leakage 
resistance paths, which in turn could cause nuisance 
shutdowns of main burner.
Flame rod and porcelain insulators should be periodically 
examined for oil or soot deposits. Such deposits should be 
cleaned off before unit is put back in replace. 
The performance of the C7007A Holder (with flame rod) and 
C7008A, C7009A Flame Rod Assemblies can be determined 
by measuring the flame signal (current/voltage) during pilot 
burner operation.
Most existing Honeywell flame safeguard controls incorporate 
a flame signal jack on the amplifier or the control itself. The 
flame current measurement is made with a volt-ohm-meter 
such as the Honeywell W136A Meter or a microammeter with 
a zero to 25 microampere scale. A meter connector plug (part 
no. 196146, provided with the W136A) is used to adapt the 
W136A to the flame current jack on the flame safeguard 
control. The W136A Meter probes are connected to the two 
ends of the connector plug (red to red, black to black). The 
plug end of the connector inserts directly into the flame current 
jack of the flame safeguard control (see Fig. 11). If the flame 
safeguard control does not have a meter jack, or if a meter 
connector plug is not available, a meter can be wired in series 
with the "F" lead of the flame detector circuit. During the 
burner run cycle, the minimum acceptable flame current is two 
microamperes.
The Honeywell BCS 7700 and 7800 SERIES controls provide 
for a voltage flame signal measurement. A 20,000 ohm/volt 
meter with a zero to 5 or 10 Vdc scale is recommended for the 
BCS 7700 measurement and a one megohm/volt meter is 
suggested for the 7800 SERIES controls. The flame signal 
measurement is made by inserting the positive (red) meter 
probe into the control positive (+) jack and the negative (black) 
probe into the negative (-) jack of the BCS 7700 or the (-Com) 
jack of the 7800 SERIES control (see Figs. 12, 13). With the 
system in operation, the minimum acceptable flame signal 
voltage is 1.25 Vdc for the 7800 SERIES controls and 2.2 Vdc 
for the BCS 7700 control.
A low flame signal reading indicates the photocell is not 
receiving sufficient visible flame radiation. Low flame currents 
can be the result of an improperly positioned sight pipe, 
restricted field of view, contaminated protective window or 
focusing lens, or a defective photocell. Flame signals of 4 to 6 
microamperes for existing controls and up to 5 Vdc for the 
BCS 7700 and 7800 SERIES controls can be expected on 
good applications/installations.
Fig. 10. Measuring microamp flame signal.
Fig. 11. Measuring BCS 7700 controls flame signal 
voltage.
W136A VOLT-
OHMMETER
W136A SELECTOR
SWITCH
196146 METER
CONNECTOR
PLUG
PLUG
FLAME SIGNAL
METER JACK
PLUG-IN FLAME
SIGNAL AMPLIFIER
RED CONNECTOR
BLACK CONNECTORBLACK (-) METER LEAD
RED (+)
METER
LEAD
M6532A
RESET
BUTTON
B
PROGRAM
MODULE
20,000
VOLT-
OHM METER
V
O
METER
PROBES
P
FLAME
AMPLIFIER
BCS 7700 CHASSIS MODULE FOOT MOUNT
M7860