EasyManua.ls Logo

Honeywell C7110C1040 - Configuration Potentiometer Modes

Honeywell C7110C1040
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C7110C1040 AND C7110C1080 WALL MODULES – PRODUCT DATA
5 EN0B-0775GE51 R0619
"DEBUG"
Fig. 10. Do not set jumper set to DEBUG!
DO NOT USE!
Configuration Potentiometer
The wall module features a configuration potentiometer
(accessible only after removing the top cover) which can be
used to configure the output of terminal 2 (CO
2
level) and
(when in the "Relay Output" mode) the "Threshold Level
(ppm)".
SERVICE LED
MAX.
OFF
SERVICE
LED IS LIT
SERVICE LED
FLASHES
MIN.
SERVICE
LED IS DARK
50% =
1000 ppm
ACTUAL CO2
CONCENTRATION
(EXAMPLE)
Fig. 11. Configuration potentiometer (e.g., set to 50% =
1000 ppm)
The CO
2
output can operate in two modes:
To select the "Sensor Output" mode (analog), set the
configuration potentiometer to "OFF" (default setting) (see
Fig. 11). See also Fig. 12.
To select the "Relay Output" mode (digital), set the con-
figuration potentiometer to between the "MIN." and "MAX."
markers (see Fig. 11). The hysteresis value is
permanently set to 100 ppm. See also Fig. 13.

Other manuals for Honeywell C7110C1040

Related product manuals