MERLIN NX IP AND MST/TP VAV CONTROLLER - INSTALLATION INSTRUCTIONS
EN1Z-1076GE51 R0722 10
The actuator mounts directly onto the VAV box damper 
shaft and has up to 44 in-lb. (5 Nm) torque, 90-degree 
stroke, and 108 second timing at 50 Hz and 90 second 
timing at 60 Hz.
The actuator is shipped with two mechanical end limit set 
screws to control the amount of rotation from 12° to 95°. 
These set screws must be securely fastened in place. To 
ensure tight closing of the damper, the shaft adapter has a 
total rotation stroke of 95°.
Fig. 10. Setting the mechanical end limits
NOTE: The actuator is shipped with the mechanical end-
limit set screws set to 95° of rotation.
Adjust the two set screws closer together to reduce 
the rotation travel. Each “hash mark” indicator on 
the bracket represents approximately 6.5° of rota-
tion per side.
The Declutch button, when pressed, allows you to 
rotate the universal shaft adapter.
The unit is shipped with the actuator set to rotate open in 
the clockwise (CW) direction to a full 95°. The extra 5° 
ensures a full opening range for a 90⁰ damper. The 
installation procedure varies depending on the damper 
opening direction and angle:
1. If the damper rotates clockwise (CW) to open, and the 
angle of the damper open-to-closed is 90°:
a. Manually open the damper fully (rotate clockwise).
b. Using the Declutch button, rotate the universal shaft 
adapter fully clockwise. 
c. Mount the actuator to the VAV damper box and shaft.
d. Tighten the two bolts on the centering clamp (8 mm 
wrench; 70 lb.-in. [8 Nm] torque). When the actuator 
closes, the damper rotates CCW 90 degrees to fully 
close.
2. If the damper rotates clockwise (CW) to open, and the 
angle of the damper open-to-closed is 45 or 60 degrees: 
a. Manually open the damper fully (rotate clockwise).
b. The actuator is shipped with the mechanical end limits 
set at 95 degrees. Adjust the two mechanical end-limit 
set screws to provide the desired amount of rotation. 
Adjust the two set screws closer together to reduce the 
rotation travel. 
c. Tighten the two mechanical end-limit screws (Phillips #2 
screwdriver; (26.5-31 lb.-in. [3.0-3.5 Nm] torque).
d. Using the Declutch button, rotate the universal shaft 
adapter fully clockwise.
e. Mount the actuator to the VAV damper box and shaft.
f. Tighten the two bolts on the centering clamp (8 mm 
wrench; 70 lb. in. [8-10 Nm] torque). 
g. When the actuator closes, the damper rotates CCW 
either 45 or 60 degrees to fully close.
3. If the damper rotates counterclockwise (CCW) to open, 
and the angle of the damper open-to-closed is 90 
degrees:
a. Manually open the damper fully (rotate counterclock-
wise).
b. Using the Declutch button, rotate the universal shaft 
adapter fully counterclockwise.
c. Mount the actuator to the damper box and shaft.
d. Tighten the two bolts on the centering clamp (8 mm 
wrench; 70 lb.-in. [8Nm] torque). When the actuator 
closes, the damper rotates CW 90 degrees to fully close.
4. If the damper rotates counterclockwise (CCW) to open, 
and the angle of the damper open-to-closed is 45 or 60 
degrees:
a. Manually open the damper fully (rotate counterclock-
wise).
b. The actuator is shipped with the mechanical end limits 
set at 95 degrees. Adjust the two mechanical end-limit 
set screws to provide the desired amount of rotation. 
Adjust the two set screws closer together to reduce the 
rotation travel.
c. Tighten the two mechanical end-limit screws (Phillips #2 
screwdriver; (26.5-31 lb.-in. [3.0-3.5 Nm] torque).
d. Using the Declutch button, rotate the universal shaft 
adapter fully counter-clockwise.
e. Mount the actuator to the VAV damper box and shaft. 
f. Tighten the two bolts on the centering clamp (8 mm 
wrench; 70 lb.-in. [8Nm] torque). 
g. When the actuator closes, the damper rotates CW either 
45 or 60 degrees to fully close.
Airflow Sensor Connection
Connect the air flow pickup to the two restrictor ports on the 
controller.
NOTE:
Use 1/4 in. (6 mm Outside diameter and 5 mm inner 
diameter), with a 3/64 in. (1 mm) wall thickness, ple-
num-rated 1219 FR (94V-2) tubing.
You should always use a fresh cut on the end of the 
tubing that connects to the air flow pickups and the 
restrictor ports on the controller. Secure the connec-
tion using a zip tie (procured locally).