LONWORKS BUS I/O MODULES – PRODUCT DATA
EN0Z-0980GE51 R0119
12
Binary Input Module
3
4
2
1
Fig. 15. CLIOP823A
LONWORKS Bus BI Module (shown with
XS823 terminal socket)
Legend
1 LONWORKS service button S1
2 Status LEDs
3 Service LED
4 Power LED
NOTE: The hex switch S2 (located next to the L
ONWORKS
service S1) has no function in combination with a
L
ONWORKS Bus I/O module. It is used with Panel
Bus I/O modules, only.
The CentraLine L
ONWORKS Bus Binary Input Module, with 12
binary inputs, is installed with the XS823 or XSU823 Terminal
Socket.
Configuration as Fast Totalizer
Using CARE / COACH AX / COACH NX, the binary inputs
can be configured as fast totalizers for operation in con-
junction with devices equipped with an open collector output.
Table 5. Binary inputs used as fast totalizers
Frequency
max. 20 Hz
Pulse ON
min. 25 ms
Pulse OFF
min. 25 ms
Bounce
max. 5 ms
FAST
TOTALIZER
DRY CONTACT
4 ... 40 VDC = OPEN
0 ... 2 VDC = CLOSED
150 kOHM
10 kOHM
18 VDC (NOT STABILIZED)
+V
BI
GND
Fig. 16. Configuration of a binary input as a fast totalizer
71
75
72
76
73 77
74
GND GND GND GND GND GND GND GND GND GND GND GND
1
BI1 BI2
BI3
BI4
BI5 BI6
BI7
BI8 BI9 BI10
BI11 BI12
2
3
13
4
14
5
15
6
16
7
17
8 9 10
11 12
18 19 20
21 22
23
24
25 26
78
COM
A
COM
A
COM
B
COM
B
24
V~
24
V
~
24
V~0
24
V
~0
Fig. 17. CentraLine L
ONWORKS Bus Binary Input Modules
(schematic)
Features
Static binary input (dry contact)
Totalizer for up to 20 Hz
LEDs per binary input supporting alarm display mode
(red/green) or status mode (off/yellow).
Color mode of each LED can be set to OFF/yellow or
green/red in CARE / COACH AX / COACH.