LONWORKS BUS I/O MODULES – PRODUCT DATA
EN0Z-0980GE51 R0119
8
Analog Output Modules
2
4
5
3
1
Fig. 10. CLIOPR822A LonWorks Bus AO Module (shown
with terminal socket)
Legend
1 LONWORKS service button S1
2 Manual overrides
3 Status LEDs
4 Service LED
5 Power LED
NOTE: The hex switch S2 (located next to the L
ONWORKS
service S1) has no function in combination with a
L
ONWORKS Bus I/O module. It is used with Panel
Bus I/O modules, only.
The CentraLine L
ONWORKS Bus Analog Output Modules, with
8 analog outputs, are available in the following models:
CLIOL822A L
ONWORKS Bus Analog Output Module
(without manual overrides)
CLIOLR822A L
ONWORKS Bus Analog Output Module (with
manual overrides)
They are installed with the XS821-22 or XSU821-22 Terminal
Socket.
71
75
72
76
73 77
74
21
9
GND GND GND GND GND GND GND GND GND GND
22
10
1
11
AO1
NC NC
AO2 AO3 AO4
O5 AO6 AO7
AO8
2
12
3
13
4
14
5
15
6
16
7
17
8
18 25 26
78
COM
A
COM
A
COM
B
COM
B
24
V~
24
~
24
V~0
24
~0
Fig. 11. CentraLine L
ONWORKS Bus Analog Output
Modules (schematic)
Features
0…11 VDC, +/-1 mA
Floating actuator (requires MCD3)
Binary output (0 V / 10 V)
red LED per output (brightness according to signal level)
Optional versions with manual override potentiometers
(Auto, 0…100%; LED flashes in override mode)
Feedback on manual override signal
8-bit resolution
Configurable safety position for outputs in case of
communication problems (remain, 0%, 50%, 100%)