EasyManua.ls Logo

Honeywell CentraLine CLIOL822A - Analog Output Modules

Honeywell CentraLine CLIOL822A
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LONWORKS BUS I/O MODULES – PRODUCT DATA
EN0Z-0980GE51 R0119
8
Analog Output Modules
2
4
5
3
1
Fig. 10. CLIOPR822A LonWorks Bus AO Module (shown
with terminal socket)
Legend
1 LONWORKS service button S1
2 Manual overrides
3 Status LEDs
4 Service LED
5 Power LED
NOTE: The hex switch S2 (located next to the L
ONWORKS
service S1) has no function in combination with a
L
ONWORKS Bus I/O module. It is used with Panel
Bus I/O modules, only.
The CentraLine L
ONWORKS Bus Analog Output Modules, with
8 analog outputs, are available in the following models:
CLIOL822A L
ONWORKS Bus Analog Output Module
(without manual overrides)
CLIOLR822A L
ONWORKS Bus Analog Output Module (with
manual overrides)
They are installed with the XS821-22 or XSU821-22 Terminal
Socket.
71
75
72
76
73 77
74
21
9
GND GND GND GND GND GND GND GND GND GND
22
10
1
11
AO1
NC NC
AO2 AO3 AO4
A
O5 AO6 AO7
AO8
2
12
3
13
4
14
5
15
6
16
7
17
8
18 25 26
78
COM
A
COM
A
COM
B
COM
B
24
V~
24
V
~
24
V~0
24
V
~0
Fig. 11. CentraLine L
ONWORKS Bus Analog Output
Modules (schematic)
Features
0…11 VDC, +/-1 mA
Floating actuator (requires MCD3)
Binary output (0 V / 10 V)
red LED per output (brightness according to signal level)
Optional versions with manual override potentiometers
(Auto, 0…100%; LED flashes in override mode)
Feedback on manual override signal
8-bit resolution
Configurable safety position for outputs in case of
communication problems (remain, 0%, 50%, 100%)