COMFORTPOINT PROGRAMMABLE LON, VAV/UNITARY CONTROLLERS
5 62-0288—03
Panel Mounting
The controller enclosure is constructed of a plastic base plate 
and a plastic factory-snap-on cover. 
NOTE: The controller is designed so that the cover does not 
need to be removed from the base plate for either 
mounting or wiring.
The controller mounts using four screws inserted through the 
corners of the base plate. Fasten securely with four No. 6 or 
No. 8 machine or sheet metal screws.
The controller can be mounted in any orientation. Ventilation 
openings are designed into the cover to allow proper heat 
dissipation, regardless of the mounting orientation.
DIN Rail Mounting (CP-UL1012S, CP-UL4024S, 
CP-UL6438S, CP-VL4024NS, and CP-VL6438NS)
To mount the CP-UL1012S, CP-UL4024S, CP-UL6438S, 
CP-VL4024NS, or CP-VL6438NS controller on a DIN rail 
[standard EN50022; 1-3/8 in. x 9/32 in. (7.5 mm x 35 mm)], 
refer to Fig. 8 and perform the following steps:
1. Holding the controller with its top tilted in towards the 
DIN rail, hook the two top tabs on the back of the con-
troller onto the top of the DIN rail.
2. Push down and in to snap the two bottom flex connec-
tors of the controller onto the DIN rail.
Fig. 8. Controller DIN rail mounting (models CP-UL1012S, 
CP-UL4024S, CP-UL6438S, CP-VL4024NS, and 
CP-VL6438NS).
IMPORTANT
To remove the controller from the DIN rail, perform the 
following:
1. Push straight up from the bottom to release the top 
tabs.
2. Rotate the top of the controller out towards you and 
pull the controller down and away from the DIN rail to 
release the bottom flex connectors.
Piping (CP-VL0000AS, CP-VL4022AS, 
CP-VL4024NS, CP-VL6436AS, and 
CP-VL6438NS)
Air flow Pickup
For CP-VL0000AS, CP-VL4022AS, CP-VL4024NS, 
CP-VL6436AS, and CP-VL6438NS, connect the air flow pickup 
to the two restrictor ports on the controller (see Fig. 9).
NOTES:
— Use 1/4 inch (6 mm) outside diameter, with a 
0.040 in. (1 mm) wall thickness, plenum-rated 
1219 FR (94V-2) tubing.
— Always use a fresh cut on the end of the tubing 
that connects to the air flow pickups and the 
restrictor ports on the controller.
Connect the high pressure or upstream tube to the plastic 
restrictor port labeled (
+), and the low pressure or 
downstream tube to the restrictor port labeled (
-). See labeling 
in Fig. 9. When twin tubing is used from the pickup, split the 
pickup tubing a short length to accommodate the connections.
NOTES:
— If controllers are mounted in unusually dusty or 
dirty environments, an inline, 5-micron disposable 
air filter (use 5-micron filters compatible with 
pneumatic controls) is recommended for the high 
pressure line (marked as +) connected to the air 
flow pickup.
— The tubing from the air flow pickup to the control-
ler should not exceed three feet (0.914 m). Any 
length greater than this will degrade the flow 
sensing accuracy.
— Use caution when removing tubing from a 
connector. Always pull straight away from the 
connector or use diagonal cutters to cut the edge 
of the tubing attached to the connector. Never 
remove by pulling at an angle.
Fig. 9. Air flow pickup connections (CP-VL0000AS, 
CP-VL4022AS, CP-VL4024NS, CP-VL6436AS, and 
CP-VL6438NS).
DIN RAIL
TOP TABS
BOTTOM FLEX
CONNECTORS
M16815
M23556A
AIR FLOW 
PICKUP 
ΔP 
1 
2 
3 4 5 6 
7 8 
1 0 9  2 3 4 5 6 7 8  0 9 
1 1  1 1 1 1 1 1 1  2 1 
1 
2 
3 4 
5 
6 
7 8 
0 
9 
2 
2 2 
2 2 
2 
2 
2 2 
3 
3 
1 
2 
3 4 
5 
6 
7 8 
0 
9 
3 
3 
3 
3 3 
3 3 
3 4 
RESTRICTOR 
PORT 
RESTRICTOR 
PORT 
CONNECTOR 
TUBING