COMFORTPOINT PROGRAMMABLE LON, VAV/UNITARY CONTROLLERS
7 62-0288—03
NOTE: Controller configurations are not necessarily limited 
to three devices, but the total power draw, including 
accessories, cannot exceed 100 VA when powered 
by the same transformer (U.S. only). For power 
wiring recommendations, see “Wiring” on page 6.
Fig. 12. Power wiring details for two or more controllers per transformer. 
Wiring Method
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect power supply before beginning wiring, or 
making wiring connections, to prevent electrical shock 
or equipment damage.
NOTE: When attaching two or more wires to the same termi-
nal, other than 14 AWG (2.0 sq mm), be sure to twist 
them together. Deviation from this rule can result in 
improper electrical contact (see Fig. 13).
Each terminal can accommodate the following gauges of wire:
— Single wire: from 22 AWG to 14 AWG solid or stranded
— Multiple wires: up to two 18 AWG stranded, with 1/4 watt 
wire-wound resistor
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in 
the required terminal location and tighten the screw.
3. If two or more wires are being inserted into one terminal 
location, twist the wires together a minimum of three 
turns before inserting them (see Fig. 13).
4. Cut the twisted end of the wires to 3/16 in. (5 mm) 
before inserting them into the terminal and tightening 
the screw.
5. Pull on each wire in all terminals to check for good 
mechanical connection.
Fig. 13. Attaching two or more wires at terminal blocks.
Controller Replacement (CP-VL0000AS, 
CP-VL4022AS, and CP-VL6436AS)
For CP-VL0000AS, CP-VL4022AS, and CP-VL6436AS 
controllers, which are hard-wired to an actuator, perform the 
following actions to replace the complete assembly (controller 
and actuator):
1. Remove all power from the controller.
2. Remove the two air flow pickup connections from the 
pressure sensor.
3. Remove the terminal blocks.
4. Remove the old controller and actuator assembly from 
its mounting.
M23559A
120/240 
VAC 
TRANSFORMER 
OUTPUT 
DEVICE 
POWER 
ΔP 
1 
2 
3 4 5 6 
7 8 
1 0 9  2 3 4 5 6 7 8  0 9 
1 1  1 1 1 1 1 1 1  2 1 
1 
2 
3 4 
5 
6 
7 8 
0 
9 
2 
2 2 
2 2 
2 
2 
2 2 
3 
3 
1 
2 
3 4 
5 
6 
7 8 
0 
9 
3 
3 
3 
3 3 
3 3 
3 4 
COM 
24 VAC 
ΔP 
1 
2 
3 4 5 6 
7 8 
1 0 9  2 3 4 5 6 7 8  0 9 
1 1  1 1 1 1 1 1 1  2 1 
1 
2 
3 4 
5 
6 
7 8 
0 
9 
2 
2 2 
2 2 
2 
2 
2 2 
3 
3 
1 
2 
3 4 
5 
6 
7 8 
0 
9 
3 
3 
3 
3 3 
3 3 
3 4 
EARTH 
GROUND (TERMINAL 3) 
ΔP 
1 
2 
3 4 5 6 
7 8 
1 0 9  2 3 4 5 6 7 8  0 9 
1 1  1 1 1 1 1 1 1  2 1 
1 
2 
3 4 
5 
6 
7 8 
0 
9 
2 
2 2 
2 2 
2 
2 
2 2 
3 
3 
1 
2 
3 4 
5 
6 
7 8 
0 
9 
3 
3 
3 
3 3 
3 3 
3 4 
EARTH 
GROUND (TERMINAL 3) 
EARTH 
GROUND (TERMINAL 3) 
CONNECT POWER TO  
TERMINALS 1 AND 2 
1/2
(13)
STRIP 1/2 IN. (13 MM) 
FROM WIRES TO 
BE ATTACHED AT 
ONE TERMINAL.
1.
2.
TWIST WIRES 
TOGETHER WITH 
PLIERS (A MINIMUM 
OF THREE TURNS).
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) 
BEFORE INSERTING INTO TERMINAL AND 
TIGHTENING SCREW. THEN PULL ON EACH 
WIRE IN ALL TERMINALS TO CHECK FOR 
GOOD MECHANICAL CONNECTION.
M17207