• Loosen the two bolts on the actuator clamp to
release the actuator from the shaft.
• Remove the controller’s mounting screws.
• Gently pull the controller and actuator assembly
straight out, until the assembly is clear of the
actuator shaft.
5. Mount the new controller and actuator assembly (see
“Installation” on page 2).
6. Reconnect the two air flow pickup tubes to the pressure
sensor (see “Piping (CP-VL0000AS, CP-VL4022AS,
CP-VL4024NS, CP-VL6436AS, and CP-VL6438NS)” on
page 5).
7. Replace the terminal blocks:
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
8. Restore power to the controller.
9. Perform checkout.
Controller Replacement (CP-VL4024NS and 
CP-VL6438NS)
Perform the following to replace the CP-VL4024NS and 
CP-VL6438NS controllers:
1. Remove all power from the controller.
2. Remove the two air flow pickup connections from the
pressure sensor.
3. Remove the terminal blocks.
4. Remove the old controller from its mounting.
IMPORTANT 
(FOR CONTROLLERS MOUNTED TO A DIN RAIL):
1. Push straight up from the bottom to release the top
pins.
2. Rotate the top of the controller outwards to release
the bottom flex connectors (see Fig. 8 on page 5).
5. Mount the new controller.
• see “Installation” on page 2
6. Reconnect the two air flow pickup tubes to the pressure
sensor (see “Piping (CP-VL0000AS, CP-VL4022AS,
CP-VL4024NS, CP-VL6436AS, and CP-VL6438NS)” on
page 5).
7. Replace the terminal blocks:
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
8. Restore power to the controller.
9. Perform checkout.
Controller Replacement (CP-UL1012S, 
CP-UL4024S, and CP-UL6438S)
Perform the following to replace the CP-UL1012S, 
CP-UL4024S, and CP-UL6438S controllers:
1. Remove all power from the controller.
2. Remove the terminal blocks.
3. Remove the old controller from its mounting.
IMPORTANT 
(FOR CONTROLLERS MOUNTED TO A DIN RAIL):
1. Push straight up from the bottom to release the top
pins.
2. Rotate the top of the controller outwards to release
the bottom flex connectors (see Fig. 8 on page 5).
4. Mount the new controller (see “Installation” on page 2).
5. Replace the terminal blocks:
• Insert each terminal block onto its alignment pins.
• Press straight down to firmly seat it.
• Repeat for each terminal block.
6. Restore power to the controller.
7. Perform checkout.
By using this Honeywell literature, you agree that Honeywell will have no 
liability  for  any  damages arising out of  your  use  or  modification  to,  the 
literature.  You  will  defend  and  indemnify  Honeywell,  its  affiliates  and 
subsidiaries,  from and  against  any liability, cost,  or damages, including 
attorneys’ fees,  arising out  of, or resulting from, any  modification to  the 
literature by you.