Installation
4 DC1010/1020/1030/1040 Product Manual 8/05
2.2 Condensed Specifications
Honeywell recommends that you review and adhere to the operating limits listed in Table
2-1 when you install your controller.
Table 2-1 Condensed Specifications
TECHNICAL DATA
Type of Input
TC (K, J, R, S, B, E, N, T, W, PL II, U, L)
RTD (Pt100, JPt100, JPt50)
Linear (4 – 20mA)
Input Sampling Time 500 ms
PV Input
Input Resolution 14 bit (each)
PV/SP Indication 4-digit, 7 segment display
Constant Value Storage
System
Non-volatile memory (EEPROM)
Indication
Indication Accuracy
± 0.5%FS
Proportional Band (P) 0~200% (On/Off action at P=0)
Integral Time (I) 0~3600 sec (PD action at I=0)
Derivative Time (D) 0~900 sec (PI action at D=0)
Control Mode
Cycle Time 0~150 sec (4~20mAÆ 0, SSRÆ1, relayÆ10)
Relay Output Contact, SPST(DC1010)/SPDT(1020,1030,1040), 3A/240VAC
Voltage Output Voltage Pulse, 20VDC/20mA
Linear Output 4~20mA, 0~5V, 0~10V, 1~5V, 2~10V
Motor Control Output Three Position Step Control (Time proportional motor control)
Output
Others
1ϕ SSR, 3ϕ SSR, 1ϕ SCR, 3ϕ SCR
Channel 3 channels (optional)
Mode 17 alarm mode available
Alarm
Timer Flicker alarm, continued alarm, on delay timer alarm
Output Signal SP, PV
Aux. Output
Type of Output 4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V
Type of Input 4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V 2
nd
Input
(RSP)
Sampling Time 500 ms
Pattern/Segment 2 pattern/ 8 segment (each)
Program
Availability Pattern link & repeat, program/segment end alarm
Communication Type of Communication RS-232, RS-485
Rated Power Supply
Voltage & Frequency
AC 100-240V, 50/60Hz or DC15-50V, 4VA
Power Consumption Max. 8VA
Storage Temperature
-25°C~65°C
Ambient Temperature
0°C~50°C
General
Specifications
Ambient Humidity 50~85% RH (no condensation)

Table of Contents

Other manuals for Honeywell DC1040

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell DC1040 and is the answer not in the manual?

Honeywell DC1040 Specifications

General IconGeneral
Control TypePID, ON/OFF
DisplayDual 4-digit LED
Alarm OutputUp to 2 relay outputs
Accuracy±0.3% of full scale
MountingPanel mount
Input TypeThermocouple, RTD
Output TypeRelay
Power Supply100-240 VAC
Operating Temperature0 to 50°C
CommunicationRS485 Modbus