EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS INSTALLATION INSTRUCTIONS
EN1B-0304GE51 R0916M
7
Table 6. W7754S,V Output assignments
output
type
stage
OUT1 OUT2
AO (W7754V,
only)
19 20 21 22 12
1-stage
0 -- OFF -- OFF --
1 -- ON -- ON --
PWM -- -- PWM -- PWM
If OUT1 is con-
figured for “PWM”
and fan is not
configured for
“variable-speed
fan”, AO runs in
parallel to OUT1
thermal -- --
ON /
OFF
--
ON /
OFF
--
Analog Inputs
The unit is equipped with two analog inputs (for connection to
a room sensor and to a wall module with temperature setpoint
adjustment, respectively).
Table 7. Analog input usage
analog input wall module
AI1 room sensor
1)
AI2 setpoint adjustment
1) If sensor measures a temperature outside range of 0...70
°C, this is interpreted as a sensor break / short circuit.
Analog Output
The W7754R, W7754T, and W7754V feature an analog
output which can be used to control
a variable speed fan, or
a proportional valve (provided that, via the LNS plug-in,
OUT1 has been configured for “PWM” and the fan has not
been configured for “variable speed fan”), or
a 6-way valve (provided that, via the LNS plug-in, OUT1
has been configured for “Not USED,” OUT2 has been
configured for the “Changeover Mode” of type “Floating
Mid,” and the fan is not using the analog output (no fan or
1…3-speed fan)).
Table 8. Analog output usage
voltage / current
0…10 V, -1 / +5 mA
resolution
8 bit
NOTE: Connecting 24 Vac to the analog output will damage
the hardware.
Table 9. Use of the analog output
function fan output
1 mode
output
1 type
output
2 mode
output
2 type
var.-speed fan var.-
speed fan
don’t
care
don’t
care
don’t
care
don’t
care
0…10 V actu-
ator with prop.
characteristic
no fan or
1…3-
speed fan
heat,
cool or
change-
over
PWM don’t
care
don’t
care
0…10 V actu-
ator with
“floating mid”
characteristic
no fan or
1…3-
speed fan
change-
over
mode
floating
mid
not used -
2…10 V actu-
ator with 6-way
valve charac-
teristic
no fan or
1…3-
speed fan
not used - change-
over
mode
floating
mid
10.0 V
AO (0...100% = 0...10 V),
no feedback on LonWorks network
no heat, no cool
OUTPUT 1
5.0 V
0.0 V
100%
0%
nvoCoolOutput nvoHeatOutput
nvoFCUStatus.output_position[0]
100%
100%
0% 0%
Fig. 7. Operational sequence with “floating mid
characteristic” on the analog output (0….10 V)