Falcon MJ M-Bus Operating instructions
05/18 Generation 1.2
Page 7 of 38
3.3 Falcon MJ tab card
This tab card shows the current settings and values for the Falcon MJ M-Bus. The entry fields
and control buttons, described below, permit device parameters to be changed:
Primary address
is the M-Bus address of the Falcon MJ. A value between 0 and 250 can be
entered into this field if the primary address needs to be changed. Click on
"Write" control button will transfer the primary address and other alterable
settings on this tab card to the Falcon MJ module. The addresses 253, 254
and 255 are broadcast addresses.
253 -> deselect all slaves
254 -> select all slaves
255 -> select all slaves without confirmation (0xE5).