IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017 142
Supervisory
The system
detects a
supervisory
condition.
A Supervisory
with a CO
detector.
The system will report events to the central
station.
The on-board annunciator sounds a loud,
pulsing beep to distinguish supervisory
signals. For Fire Supervisory the sequence is
two seconds on, two seconds off. For ECS
Supervisory, the sequence is two seconds on,
three seconds off.
SUPERVISORY LED is on.
The LCD displays a screen similar to this one.
Press down arrow to view the fire supervisory
condition. A screen similar to this one displays.
Press SILENCE to silence the annunciator.
Trouble
A system trouble
condition occurs.
The system will report events to the central
station.
The on-board annunciator sounds a loud,
pulsing beep in the sequence ¾ of second on,
eight seconds off.
SYSTEM TROUBLE LED is on.
The LCD displays a screen similar to this one.
Press down arrow to view the fire trouble. A
screen similar to this one displays.
Press SILENCE to silence the annunciator.
Once the trouble condition has been fixed, the
system will restore itself automatically.
Prealarm
A single detector
trips in a 2-Count
zone. (2-Count
means two
detectors must
trip before an
alarm is
reported.)
Touchpad PZT beeps.
The LCD displays a screen similar to this one.
Press down arrow to view the Prealarm. A screen
similar to this one.
All system operations are available in this mode.
Reset The RESET
button is pressed
followed by a
valid code, if
necessary.
All LEDs are on briefly then the LCD displays
“RESET IN PROGRESS”. If the reset process
completes normally, the date and time normal
mode screen displays.
Menus are not available during the reset process.
Operation
Mode
Occurs When System Behavior In This Mode You Can
Table 10.2 Operations Mode Behavior