15 IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
5824 Serial / Parallel Module
(4 max.) Standby/Alarm: 45 mA mA mA
RPS-1000 Power Supply
(16 max.) Standby/Alarm: 10 mA mA mA
5496 NAC Expander
Standby/Alarm: 10 mA mA mA
5865-4 LED Annunciator Module
(with reset and silence switches)
(8 max.) Standby: 35 mA mA
Alarm: 145 mA mA
5865-3 LED Annunciator Module
Standby: 35 mA mA
Alarm: 145 mA mA
5880 LED I/O Module
Standby: 35 mA mA
Alarm: 200 mA mA
5883 Relay Interface
(32 max.) Standby: 0 mA mA
Alarm: 220 mA
(22 mA per relay)
mA
ECS-50W or ECS-125W Audio
Amplifier with/without ECS-CE4
(8 max.) Standby: 10 mA mA
Alarm: 10 mA mA
ECS-DUAL50W
(8 max.) Standby/Alarm: 10 mA mA mA
ECS-50WBU
(8 max.) Standby/Alarm: 10 mA mA mA
ECS-INT50W Internal Amplifier
(8 max.) Standby: 52 mA mA
Alarm @ 25V: 275 mA mA
Alarm @ 70V: 310 mA
mA
ECS-NVCM Network Voice Control
Module
(1 max.) Standby/Alarm: 59 mA mA mA
ECS-VCM Voice Control Module
Standby: 70 mA mA
Alarm: 100 mA mA
ECS-SW24 Switch Expander
(8 max.) Standby: 10 mA mA
Alarm: 25 mA mA
ECS-RPU Remote Paging Unit
(7 max.) Standby: 70 mA mA
Alarm: 100 mA mA
ECS-LOC Local Operating Console
(includes RA-2000, RVM & SW-24)
(7 max.) Standby: 100 mA mA
Alarm: 150 mA mA
Network Cards
SK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21 mA
mA mA
SK-FML Fiber Optic Multi Mode (1 Max.) Standby/Alarm: 53 mA
mA mA
SK-FSL Fiber Optic Single Mode (1 Max.) Standby/Alarm: 79 mA
mA mA
A Total System Current
Wireless Modules
WIDP-WGI Wireless Gateway Max current using ext supply 40 mA
mA mA
Max current SLC Power 24 mA
mA mA
Total System Current
Auxiliary Devices
5
Refer to devices manual for current rating.
IPDACT-2 IP Communicator (1 max.) Standby: 93 mA
mA
Alarm: 136 mA
mA
IPDACT-2UD IP Communicator (1 max.) Standby: 98 mA
mA
Alarm: 155 mA
mA
CELL-MOD/CELL-CAB-SK Standby: 55 mA
mA
Alarm: 100 mA
mA
Alarm/Standby: mA
mA mA
Alarm/Standby: mA
mA mA
Alarm/Standby: mA
mA mA
Alarm/Standby: mA
mA mA
B
Auxiliary Devices Current
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
Table 3.2 Current Draw Worksheet for IDP SLC Devices