21 IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Accessories Modules
5815XL SLC Expander (63 max.) Standby/Alarm: 80 mA
mA mA
RA-2000 Remote LCD Annunciator (16 max.) Standby: 25 mA
mA
Alarm: 50 mA
mA
RA-1000 Remote LCD Annunciator Standby: 20 mA
mA
RA-100 Remote LCD Annunciator Standby: 20 mA
mA
Alarm: 25 mA
mA
5824 Serial/Parallel Printer Interface (4 max.) Standby/Alarm: 45 mA
mA mA
RPS-1000 Power Supply (16 max.) Standby/Alarm: 10 mA
mA mA
5496 NAC Expander Standby/Alarm: 10 mA
mA mA
5865-4 LED Annunciator Module
(with reset and silence switches)
(8 max.) Standby: 35 mA
mA
Alarm: 145 mA
mA
5865-3 LED Annunciator Module Standby: 35 mA
mA
Alarm: 145 mA
mA
5880 LED I/O Module Standby: 35 mA
mA
Alarm: 200 mA
mA
5883 Relay Interface (32 max.) Standby: 0 mA
mA
Alarm: 220 mA
(22 mA per relay)
mA
ECS-50W or ECS-125W Audio
Amplifier with/without ECS-CE4
(8 max.) Standby: 10 mA
mA
Alarm: 10 mA
mA
ECS-DUAL50W (8 max.) Standby/Alarm: 10 mA
mA mA
ECS-50WBU (8 max.) Standby/Alarm: 10 mA
mA mA
ECS-INT50W Internal Amplifier (8 max.) Standby: 52 mA
mA
Alarm @ 25V: 275 mA
mA
Alarm @ 70V: 310 mA
mA
ECS-NVCM Network Voice Control
Module
(1 max.) Standby/Alarm: 59 mA
mA mA
ECS-VCM Voice Control Module Standby: 70 mA
mA
Alarm: 100 mA
mA
ECS-SW24 Switch Expander (8 max.) Standby: 10 mA
mA
Alarm: 25 mA
mA
ECS-RPU Remote Paging Unit (7 max.) Standby: 70 mA
mA
Alarm: 100 mA
mA
ECS-LOC Local Operating Console
(includes RA-200, RVM & SW-24)
(7 max.) Standby: 100 mA
mA
Alarm: 150 mA
mA
Network Cards
SK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21 mA
mA mA
SK-FML Fiber Optic Multi Mode (1 Max.) Standby/Alarm: 53 mA
mA mA
SK-FSL Fiber Optic Single Mode (1 Max.) Standby/Alarm: 79 mA
mA mA
A
Total System Current
Auxiliary Devices
3
Refer to devices manual for current rating.
IPDACT-2 IP Communicator (1 max.) Standby: 93 mA
mA
Alarm: 136 mA
mA
IPDACT-2UD IP Communicator (1 max.) Standby: 98 mA
mA
Alarm: 155 mA
mA
CELL-MOD/CELL-CAB-SK Standby: 55 mA
mA
Alarm: 100 mA
mA
Alarm/Standby: mA
mA mA
Alarm/Standby: mA
mA mA
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
Table 3.4 Current Draw worksheet for SD Devices