3
UL Current Draw Data
Table 2 lists the maximum UL Current Draw (mA RMS) allowed for 2-Wire Horn Strobes.
Horn Strobe Tones and Sound Output Data
Table 3 lists the horn strobe tones and sound output date.
DC Input
8-17.5 Volts 16-33 Volts
15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temporal High 103 167 71 90 143 165 187 217 254
Temporal Low 96 165 54 71 137 161 185 211 249
Non-Temporal High 106 173 71 90 141 165 187 230 273
Non-Temporal Low 95 166 54 71 124 161 170 216 258
3.1K Temp Hi 111 164 69 94 147 163 184 229 257
3.1K Temp Low 103 163 54 88 143 155 185 212 252
3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271
3.1K Non-Temporal 103 169 54 88 131 155 187 217 259
16-33 Volts
FWR Input 15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temporal High 107 135 179 198 223 254 286
Temporal Low 78 101 151 172 199 229 262
Non-Temporal High 107 135 179 198 223 254 286
Non-Temporal Low 78 101 151 172 199 229 262
3.1K Temporal High 108 135 179 200 225 256 289
3.1K Temporal Low 79 101 150 171 196 229 260
3.1K Non-Temporal High 108 135 179 200 225 255 289
3.1K Non-Temporal Low 79 101 150 171 196 229 260
Table 2 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe
Switch Position Sound Pattern dB
8–17.5
Volts
16–33
Volts
FWR
DC DC
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temporal Low 77 83 83
Table 3: Horn Strobe Tones and Sound Output Data