12/2018
Power Supply Rack Extension Kit # 51-52-33-149 1
HC900 Controller
Power Supply Rack Extension Installation
PS Rack Extension 900RPE - (current revision number)
Document Number Form: 51-52-33-149
Effective Date: 12/2018
Supersedes: 04/2005
Summary
Optional field installation kit
Installed on the rack next to the Primary
Power Supply
Provides a rack extension to hold a 2nd
(Reserve) Power Supply and Power
Status Module per I/O Rack in order to
maintain power to the rack if the Primary
Power Supply fails
Allows either Power Supply to be
replaced while maintaining power to the
rack using the other Power Supply
Available for the 8-Slot and 12-Slot I/O
Racks
Not available for the 4 Slot I/O Rack
8-Slot Rack
12-Slot Rack
8-Slot Rack
12-Slot Rack
Figure 1 PS Rac
k Extension Location
Procedure Follow the procedure in Table 1 to install a Power Supply (PS) Rack Extension to
an 8-slot or 12-slot I/O rack.
Table 1 – PS Rack Extension Installation
Step Action
1 Remove power to the rack to be extended.
2
Remove the rack from its mounting
and remove all modules from the
rack. Place the empty rack on a
flat surface with the back plate
down.
Controller CPU or Scanner Module Slot
Power Supply Slot
I/O Modules
Controller CPU or Scanner Module Slot
Power Supply Slot
I/O Modules

Other manuals for Honeywell HC900

Questions and Answers:

Honeywell HC900 Specifications

General IconGeneral
SeriesHC900
RedundancyOptional
Programming LanguageFunction Block Diagram, Ladder Logic, Structured Text
InputsAnalog, Digital
OutputsAnalog, Digital, Relay
DisplayOptional
ControlPID, Advanced Control
Power Supply24V DC or 100-240V AC
Storage Temperature-40°C to 85°C
Humidity5% to 95% non-condensing
Communication ProtocolsModbus, Ethernet