Performance Series Network Video Recorder User Guide
242
Guidelines for Connecting Local Alarm Input Ports
Ground alarm inputs. Choose from normally open (NO) or normally closed (NC).
Connect the COM end and GND end of the alarm detector in parallel. Supply external
power to the alarm detector.
Connect the ground of the NVR and the ground of the alarm detector in parallel.
Connect the NO/NC port of the alarm sensor to the NVR alarm input.
Use the same ground as the NVR if you are supplying external power to the alarm device.
Guidelines for Connecting Alarm Output Ports
Provide external power to external alarm device.
To prevent overloading, carefully review the following relay specifications:
Table 14-2 Guidelines for Connecting Alarm Output Ports
Material
Nickel/silver contacts with gold
plating
Rating
(Resistance
Load)
Rated switch capacity 30 V DC 1A; 125 V AC 0.5A
Maximum switch power 62.5 V AC, 30 W
Maximum switch voltage 125 V AC; 60 V DC