HM700A1000
33-00118—01 2
Fig. 1. Specification label location.
CAUTION
Servicing
Disconnect main power before any servicing.
The plumbing and electrical compartments contain
high voltage components and wiring. Access should
be limited to authorized personnel only.
During and following operation of the humidifier, the
steam and components in contact with the steam
such as the steam lines, steam distributors, and
condensate lines can become hot and can burn if
touched.
Honeywell does not accept any liability for installations
of humidity equipment installed by unqualified
personnel or the use of
parts/components/equipment that are not
authorized or approved by Honeywell.
To maintain warranty, only Honeywell approved parts
and cylinders may be used in the operation of the
product.
CAUTION
Electrical
All electrical work should be done according to local
and national electrical code.
Electrical connection to be performed by a licensed
electrician.
Unit must be powered by a dedicated GFI circuit.
CAUTION
Plumbing
Plumbing to be performed by a licensed plumber.
Drain water from humidifier can be very hot. Do not
drain to public sink.
All plumbing work should be done according to local
plumbing code.
CAUTION
Installation
Do not mount on hot surfaces.
Do not mount in area where freezing can occur.
Do not mount on vibrating surface.
Do not mount on floor.
The HM700 produces steam at atmospheric pressure.
No devices which could block steam output should
be connected to the steam outlet.
Steam lines must be installed so that no restriction can
produce backpressure in the humidifier.
CAUTION
Water quality
The Honeywell HM700 requires a cold water
connection from your home's main water supply
between 30-100 PSIG. A throttle valve may be
necessary, and a water shut-off valve is
recommended for safety. Reverse Osmosis (RO)
and Deionized (DI) water must not be used. Water
conductivity is important to ensure the electrode
humidifier operates effectively. Honeywell
recommends 150-1200 μS (microsiemens).
Parts and Accessories
The following parts and accessories are available and may have been included with your HM700 humidifier. The cylinder is the
only item that will need periodic replacement to maintain proper humidifier operation.
Table 2. Parts and accessories.
M35758
Golden Valley Minnesota 55422
MADE IN CANADA
MODEL:
VOLTS 1:
KW:
HM700A1000
S/N:
XXXXXXX
110-120
PHASE:
1
HZ:
60
1.4
DATE:
XXXXXXXXX
2583297A
220-240
VOLTS 2:
F.L.A: GPD:
12.0
F.L.A: GPD:
12.0
2.9
KW:
Auto-Adaptive
11
22
1
LISTED 205X
HUMIDIFIER
Part/Accessory Part Number
Replacement Cylinder HM700ACYL2
HumidiPRO Humidistat H6062A1000
Stainless Steel Distribution Remote Mount Kit HM700ADISTKIT
Replacement Drain Valve HM700ADVALVE
Replacement Fill Valve HM700AFVALVE
Replacement Transformer HM700ATX
Replacement PC Board HM700APCB
15 ft. Insulated Steam and Condensate Line Hose Kit HM700AHOSEKIT
Differential Pressure Switch for Air Proving 50027910-001

Other manuals for Honeywell HM700A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell HM700A1000 and is the answer not in the manual?

Honeywell HM700A1000 Specifications

General IconGeneral
BrandHoneywell
ModelHM700A1000
CategoryHumidifier
LanguageEnglish

Related product manuals