Cause of Error
Cause: The unit detects a short circuit or open circuit of the
outdoor unit coil sensor during the inspection of the outdoor
unit control panel, indicated by “external coil sensor error”.
Inspection path: Sensor Sensor wire Connectors
Main outdoor unit control panel
Tools Required
Multimeter, 20K standard sensor (25
Possible Broken Part External coil sensor, outdoor unit control panel
Troubleshooting
Procedures
1. Check if
there’s resistance problem, short circuit or open
circuit in the sensor; the resistance value should be
within a reasonable range (15K under the temperature
of 25)
2. Check if the sensor wire is broken.
3. Check if the terminal connectors are well fixed; check if
the weld between the terminal and the main control panel
is loose and pull the terminal slightly for inspection if
necessary.
4. Check if the sensor is damp/wet.
5. If no standard sensor is available, replace the internal
temperature sensor, and then check if the error persists;
if yes, check the main internal control panel and replace
it.
Key Details
DO NOT USE A SENSOR WITH A VALUE LOWER OR
HIGHER THAN 20K
E2 EXTERNAL COIL SENSOR ERROR

Other manuals for Honeywell HWAC-1217S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell HWAC-1217S and is the answer not in the manual?

Honeywell HWAC-1217S Specifications

General IconGeneral
BrandHoneywell
ModelHWAC-1217S
CategoryAir Conditioner
LanguageEnglish

Related product manuals