1
Flame detection device for
oil and gas flames
INTRODUCTION
The IRD 1020.1 detector is used to supervise gas or oil
flames. This flame monitoring device should be connected
to a Satronic oil burner control box. Monitoring is based on
the infra-red flicker principle, in other words, the flickering
infra-red light of the flame is detected. The steady radiation
from, for example, the glowing refractory layer on the inside
of the boiler, has no effect on the detector. The IRD 1020.1
replaces the IRD 1020 and 920.
When exchanging the IRD 1020, care must be taken that the
corresponding IRD 1020.1 with the same imprint (blue or
white) is used (see page 3 and 4).
When exchanging the IRD 920, care must be taken to wire
the sensor correctly (see page 3), and the existing holder
must be exchanged with the magnetic holder M93.
For replacement of the IRD 920 with IRD 1020.1 is the
sensor cable also needed.
The infra-red flicker detector can be used with any one of the
following control boxes:
IRD 1020.1 DKG 972
DLG 974, 976
DMG 970, 971, 972, 973
TFI 812.2
MMI 810, 811, 812, 815, 816, 962
TMG 740-2, 740-3
SGU 930, 930i
IRD 1020.1 D DVI 980, 982
MMG 810, 811
FFW 930
DKG 972
DLG 974, 976
DMG 970, 971, 972, 973
TFI 812.2
MMI 810, 811, 812, 815, 816, 962
TMG 740-2, 740-3
SGU 930, 930i
CONSTRUCTIONAL FEATURES
The infra-red sensor and the pre-amplifier are hermetically
sealed in glass and along with the electronics form an
integrated unit in the flame detector. Wiring is by way of a
plug connection. The sensitivity control and two LED’s for
indication of the flame signal are situated on the rear of the
flicker detector.
Infra-red flicker detector IRD 1020.1
TECHNICAL DATA
Supply voltage 220 / 240 V (-15... +10%)
50 Hz (50 - 60 Hz)
or 110/120 V (-15... +10%)
50 - 60 Hz (±5%)
Nominal current input approx. 4 mA
Power consumption 1 VA
Ambient temperature -20° C to +60° C
Insulation standard IP 41
Mounting attitude any
Weight 40 g
Flame viewing attitude side-on or end-on according
to type
Spectral response 800 - 1100 nm
(with daylight filter) maximum 950 nm
Frequency range 15 Hz.... 250 Hz (-12 dB)
Sensitivity adjustment range approx. 1 : 20 (26 dB)
Switch-on delay < 3.5 sec.
(after connecting
operating voltage)
Response time < 0.1 sec.
Cut-out time < 1 sec.
Approved ambient parameter max. 95% at 30° C
- for operation -20° C... +60° C
- for storage -20° C... +80° C
Build-up of ice, penetration of
water and condensing water are inadmissible
Approvals according
to European standards EN 298, as well as all other
relevant Directives and
standards
EN1C-0118SZ20 R1005
Question and Answer IconNeed help?

Do you have a question about the Honeywell IRD 1020.1 and is the answer not in the manual?

Honeywell IRD 1020.1 Specifications

General IconGeneral
BrandHoneywell
ModelIRD 1020.1
CategorySecurity Sensors
LanguageEnglish

Summary

Introduction to Infra-Red Flicker Detector IRD 1020.1

Technical Data Specifications

Provides detailed specifications including supply voltage, power consumption, and environmental limits.

Constructional Features

Describes the integrated unit design, wiring, and indicator LEDs for flame signal indication.

Technical Features and Operation

Flame Detection Capabilities

Details how the detector monitors oil and gas flames using infrared flicker detection.

Installation Guidance

Provides instructions for proper detector mounting, positioning, and environmental considerations.

Commissioning, Maintenance, and Safety

Commissioning, Maintenance, and Safety

Outlines procedures for system commissioning, maintenance, safety checks, and operational testing.

Troubleshooting and Wiring

Possible Faults and Solutions

Lists common faults during pre-purge and flame establishment with potential causes and fixes.

Terminal Connections and Wiring Diagrams

Illustrates terminal layout and provides wiring diagrams for connecting to Satronic burner control boxes.

Sensitivity Characteristics

Explains sensitivity differences between blue (standard) and white (increased) IRD-Type detectors.

Product Variants and Ordering Information

Mounting Holder and Detector Dimensions

Shows diagrams and dimensions for the M93 mounting holder and the IRD 1020.1 detector.

Product Variants and Ordering

Details available product variants, item numbers, and ordering information for flame sensors and accessories.

Related product manuals