EasyManua.ls Logo

Honeywell JADE W7220 User Manual

Honeywell JADE W7220
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
INSTALLATION INSTRUCTIONS
63-2700-11
JADE™ Economizer Module
(MODEL W7220)
PRODUCT DESCRIPTION
The JADE™ Economizer System is an expandable
economizer control system, which includes a W7220
Economizer Module (controller) with an LCD and keypad.
The W7220 can be configured with optional sensors.
The W7220 Economizer Module can be used as a stand-
alone economizer module wired directly to a commercial
set back space thermostat and sensors to provide Outdoor
Air dry-bulb economizer control.
The W7220 Economizer Module can be connected to
optional Sylk Bus sensors for single or differential
enthalpy control. The W7220 Economizer Module
provides power and communications on the Sylk Bus for
the Sylk Bus sensors.
The W7220 Economizer Module automatically detects
sensors by polling to determine which sensors are present.
If a sensor loses communications after it has been
detected, the W7220 Economizer indicates a device fail
error on its LCD.
System Components
The JADE™ Economizer System includes an Economizer
Module, 20k mixed air sensor, damper actuator, an
optional CO
2
sensor, and either a 20k outdoor air
temperature sensor or Sylk Bus sensors for measuring
Outdoor Air and return air enthalpy, temperature, and
humidity.
Economizer Module
This is the core of the JADE™ Economizer System and
includes the user interface for the system. The W7220
Economizer Module provides the basic inputs and outputs
to provide simple economizer control. When used with the
optional Sylk Bus sensors, the Economizer Module
provides more advanced economizer functionality.
Sylk Bus Sensors (optional)
The Sylk Bus Sensor is a combination temperature and
humidity sensor which is powered by and communicates
on the Sylk Bus. Up to three sensors may be configured
with the JADE™ Economizer Module. See page 2 for
details.
CO
2
Sensor (optional)
A CO
2
sensor can be added for Demand Control
Ventilation (DCV). Either an analog (2-10 Vdc) or a wall-
mount Sylk bus TR40 CO
2
sensor can be used with the
Jade economizer.
Contents
Product Description ................................................................... 1
Specifications ............................................................................... 2
Before Installation ...................................................................... 3
Installation and Setup ............................................................... 3
Mounting ........................................................................................ 3
Wiring ............................................................................................... 4
Wiring Application Examples ................................................. 9
Interface Overview ...................................................................... 18
Setup and Configuration .......................................................... 18
Checkout ......................................................................................... 31
Troubleshooting ........................................................................... 32

Other manuals for Honeywell JADE W7220

Questions and Answers:

Honeywell JADE W7220 Specifications

General IconGeneral
ModelJADE W7220
Voltage24 Vac
MemoryNon-volatile
Enclosure RatingNEMA 1
CommunicationWireless
Operating Temperature-40°F to 150°F (-40°C to 65°C)
Humidity Range5% to 95% RH (non-condensing)

Summary

INSTALLATION INSTRUCTIONS

System Components

Describes the integrated parts of the JADE™ Economizer System, including sensors and actuators.

SPECIFICATIONS

W7220A Economizer Module

Details the specifications of the W7220A Economizer Module, including user interface and capabilities.

Electrical

Covers voltage, power consumption, and output ratings for the module.

Inputs and Outputs

Details sensor inputs and actuator outputs for the economizer module.

Environmental

Specifies operating and storage temperature, and humidity limits.

INSTALLATION AND SETUP

Mounting

Procedures for mounting the JADE™ Economizer module and associated sensors.

Wiring

Instructions and examples for wiring the JADE™ Economizer module connections.

Interface and Programming Overview

Guide to navigating the JADE™ Economizer's LCD display and keypad for operation.

Setup and Configuration

Steps for configuring the JADE™ Economizer module for the specific installed system.

INTERFACE OVERVIEW

User Interface

Describes the LCD display and keypad layout of the Economizer module.

Keypad

Explains the function of the four navigation buttons for menu interaction.

CHECKOUT

Power Up

Describes the initial power-on sequence and menu display upon startup.

Status

How to check parameter values for connected devices and sensors.

Checkout Tests

How to perform tests for damper operation and configured outputs.

TROUBLESHOOTING

Alarms

Provides information on alarm messages displayed on the module's LCD.

Clearing Alarms

Steps to clear identified alarms after the cause has been removed.

Related product manuals