EasyManua.ls Logo

Honeywell JADE W7220 - Page 13

Honeywell JADE W7220
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JADE™ ECONOMIZER MODULE
13 63-2700—05
Table 5. Menu Structure
a
.
Menu Parameter
Parameter
Default
Value
Parameter
Range and
Increment
b
Notes
STATUS ECON AVAIL NO YES/NO YES = economizing available; the system can use Outdoor Air for free
cooling when required.
ECONOMIZING NO YES/NO
YES = Outdoor Air being used for 1
st
stage cooling.
OCCUPIED NO YES/NO YES = OCC signal received from space thermostat or unitary controller.
YES = 24 Vac on terminal OCC
No = 0 Vac on terminal OCC.
HEAT PUMP
n/a
c
COOL
HEAT
Displays COOL or HEAT when system is set to heat pump (non-
conventional)
COOL Y1-IN OFF ON/OFF Y1-I signal from space thermostat or unitary controller for cooling stage 1.
ON = 24 Vac on term Y1-I
OFF = 0 Vac on term Y1-I
COOL Y1-OUT OFF ON/OFF Cool Stage 1 Relay Output to stage 1 mechanical cooling (Y1-OUT
terminal).
COOL Y2-IN OFF ON/OFF Y2-I signal from space thermostat or unitary controller for second stage
cooling.
ON = 24 Vac on term Y2-I
OFF = 0 Vac on term Y2-I
COOL Y2-OUT OFF ON/OFF Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT terminal).
MA TEMP _ _._ ºF -40 to 150 ºF Displays value of measured mixed air from MAT sensor. Displays --.- if not
connected, short, or out- of-range.
DA TEMP _ _._ ºF -40 to 150 ºF Displays when Discharge Air Sylk Bus sensor is connected and displays
measured discharge air temperature.
Displays --.-°F if sensor sends invalid value, if not connected, short or out-
of-range.
OA TEMP _ _._ ºF -40 to 140 ºF Displays measured value of outdoor air temperature.
Displays --°F if sensor sends invalid value, if not connected, short or out-
of-range.
OA HUM _ _ % 0 to 100% Displays measured value of outdoor humidity from QA Sylkbus sensor.
Displays --% if not connected, short, or out- of-range.
RA TEMP _ _._ ºF 0 to 140 ºF Displays measured value of return air temperature from RAT sensor.
Displays --°F if sensor sends invalid value, if not connected, short or out-
of-range.
RA HUM _ _ % 0 to 100% Displays measured value of return air humidity from RA Sylkbus sensor.
Displays --% if sensor sends invalid value, if not connected, short or out-
of-range.
IN CO2 _ _ _ ppm 0 to 2000
(3500) ppm
Displays value of measured CO2 from CO2 sensor. Invalid if not connected,
short or out-of-range. May be adjusted in Advanced menu by Zero offset
and Span
DCV STATUS n/a ON/OFF Displays ON if above setpoint and OFF if below setpoint, and ONLY if a CO2
sensor is connected.
DAMPER OUT 2.0V 2.0 to 10.0 V
Displays output position to the damper actuator.
e
ACT POS. n/a 0 to 100% Displays actual position of actuator.
ACT COUNT n/a 1 to 65,535 Displays number of times actuator has cycled. 1 Cycle equals 180° of
movement in any direction.
ACTUATOR n/a OK/Alarm (on
Alarm menu)
Displays Error if voltage or torque is below actuator range
EXH1 OUT OFF ON/OFF Output of EXH1 terminal.
ON = relay closed; OFF = relay open.
EXH2 OUT OFF ON/OFF Output of AUX1 O terminal; displays only if AUX1 O = EXH2
ERV OFF ON/OFF Output of AUX1 O terminal; displays only if AUX1 O = ERV
MECH COOL ON 0 0, 1, or 2 Displays stage of mechanical cooling that is active.
FAN SPEED n/a LOW or HIGH Displays speed of fan on a 2-speed fan unit
W (HEAT IN) n/a ON/OFF Displays status of heat on a 2-speed fan unit.

Other manuals for Honeywell JADE W7220

Related product manuals