JADE™ ECONOMIZER MODULE
23 63-2700—05
Checkout Tests
Use the Checkout menu (Table 9) to test the damper operation
and any configured outputs. Only items that are configured are
shown in the Checkout menu.
NOTE: See “Interface Overview” on page 12. for
information about menu navigation and use of the
keypad.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the
and buttons.
2. Press the
button to select the item.
3. RUN? appears.
4. Press the button to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all parameters have been tested, press the
button (Menu up) to end the test (e.g. turn off the relay).
The checkout tests can all be performed at the time of
installation or any time during the operation of the system as a
test that the system is operable.
STATUS
(continued)
DA TEMP _ _._ ºF 0 to 140 ºF Displays when Discharge Air Sylk Bus sensor is connected
and displays measured discharge air temperature.
Displays --.-°F if sensor sends invalid value, if not connected,
short or out-of-range.
OA TEMP _ _._ ºF -40 to 140 ºF Displays measured value of outdoor air temperature.
Displays --°F if sensor sends invalid value, if not connected,
short or out-of-range.
OA HUM _ _ % 0 to 100% Displays measured value of outdoor humidity from QA
Sylkbus sensor. Displays --% if not connected, short, or out-
of-range.
RA TEMP _ _._ ºF 0 to 140 ºF Displays measured value of return air temperature from RAT
sensor. Displays --°F if sensor sends invalid value, if not
connected, short or out-of-range.
RA HUM _ _ % 0 to 100% Displays measured value of return air humidity from RA
Sylkbus sensor. Displays --% if sensor sends invalid value, if
not connected, short or out-of-range.
IN CO2 _ _ _ ppm 0 to 2000 ppm Displays value of measured CO2 from CO2 sensor. Invalid if
not connected, short or out-of-range.
DCV STATUS n/a ON/OFF Displays ON if above setpoint and OFF if below setpoint, and
ONLY if a CO2 sensor is connected.
DAMPER OUT 2.0V 2.0 to 10.0 V Displays voltage output to the damper actuator.*1
ACT POS. n/a 0-100% Command actuator position from controller
ACT COUNT n/a 0-100% Actual reported actuator position
ACTUATOR n/a OK or ALARM See alarm section for actuator alarms
EXH1 OUT OFF ON/OFF Output of EXH1 terminal.
ON = relay closed; OFF = relay open.
EXH2 OUT OFF ON/OFF Output of AUX1 O terminal; displays only if AUX1 O = EXH2
ERV OFF ON/OFF Output of AUX1 O terminal; displays only if AUX1 O = ERV
MECH COOL ON 0 0, 1, or 2 Displays stage of mechanical cooling that is active.
FAN SPEED n/a LOW or HIGH Displays speed of fan on a 2-speed fan unit
W (HEAT IN) n/a ON/OFF Displays status of heat on a 2-speed fan unit.
a
n/a = not applicable
*1 When used with Honeywell communicating actuator the damper out is in XX.X% versus XX.X Vd.
Table 8. Status Menu. (Continued)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment Notes
Table 9. Checkout Menu.
Checkout Item Checkout Test
DAMPER VMIN-HS Positions damper to VMIN position.
DAMPER VMAX-HS
(LS)
Positions damper to VMAX position. With
2-speed fan units the damper will position
to VMAX low speed fan.
DAMPER OPEN Positions damper to the full open position.
Exhaust fan contacts enable during the
DAMPER OPEN test. Make sure you pause
in this mode to allow for exhaust contacts
to energize due to the delay in the system.
DAMPER CLOSE Positions damper to the fully closed
position.
CONNECT Y1-O Closes the Y1-O relay (Y1-O).
See CAUTION on page 24
CONNECT Y2-O Closes the Y2-O relay (Y2-O).
See CAUTION on page 24