EasyManua.ls Logo

Honeywell JADE W7220 - Page 6

Honeywell JADE W7220
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JADE™ ECONOMIZER MODULE
63-2700—05 6
Sylk Bus Sensor Wiring
Use Fig. 6 and Table 3 to locate the wiring terminals for each
Sylk Bus sensor.
Use Fig. 6 and Table 4 to set the DIP switches for the desired
use of the sensor.
Fig. 6. Sylk Bus sensor DIP switches.
NOTE: When using the Sylkbus sensors there will be a
slight delay while the Jade controller and the sen-
sor communicate. Analog sensors do not commu-
nicate on the Sylkbus and output a 20k ohm
signal to the Jade controller so the response time
is instantaneous.
Actuator Wiring Options:
1. The JADE economizer controller can only have one (1)
communicating actuator connected to it.
2. Up to four (4) non-communicating and two (2) 2-position
actuators (1 each on EXH1 and AUX1 O)
3. One (1) communicating and up to four (4) non-communi-
cating and two (2) 2-position actuators (1 each on EXH1
and AUX1 O). When using a 2-position actuator on the
AUX1 O, the AUX1 O must be programmed for Exh2 and
the % open is the % open of the outdoor damper when
the 2-pos actuator opens. Connect 24 V to Exh1 and/or
AUX1 O and ground to the Jade "C" terminal.
Table 3. SYLK Bus Sensor Wiring Terminations.
Terminal
Type DescriptionNbr Label
1 S-BUS SYLK
Bus
Sylk Bus Communications
(Sensor Bus) polarity insensitive
2 S-BUS SYLK
Bus
Sylk Bus Communications
(Sensor Bus) polarity insensitive
Table 4. SYLK Bus Sensor DIP Switch Settings.
Use
DIP Switch Positions for Switches 1, 2, & 3
123
DA
a
a
DA = Discharge Air
OFF ON OFF
RA
b
b
RA = Return Air
ON OFF OFF
OA
c
c
OA = Outdoor Air
OFF OFF OFF
DIP
SWITCH
LABEL
M32271B
SYLK BUS
TERMINALS
(1 AND 2)
DIP
SWITCHES
(3)
SYLK BUS
2 PIN SIDE
CONNECTOR

Other manuals for Honeywell JADE W7220

Related product manuals