13 EN2R-9005 0406R3-NE
L4191 - L6191 DUAL AQUASTAT - DIRECT IMMERSION
SPECIFICATIONS AND DIMENSIONS
Specifications
Ambient temperature limits
0 ... 70°C
Electrical connection
6.3 mm spade terminals
Enclosure
IP40
Electrical rating:
10 A at 250 Vac, resistive load
2,5 A at 250 Vac, inductive load
15 A at 250 Vac, locked motor
250 mA at 30 mVdc (special option)
Terminal data
C-1 breaks on temperature rise
C-2 makes on temperature rise
Accessories
Immersion wells, see page 18
Fig. 7. Internal schematics
Fig. 8. Dimensional drawing L4191/L6191
+
C
+
1 C
SPST
Control
12C
+
1
SPST
Limit
SPST
Control
SPDT
Limit
C
+
1
+
C 12
SPDT
Control
SPDT
Limit
C
+
1
+
C 12
SPDT
Control
+
C 12
SPDT
Control
11.5
72
84
14.6
48
30
4
85
ϕ 5
ϕ 21
Pg 13.5
ϕ 47.1

Related product manuals