EasyManua.ls Logo

Honeywell L41.. - APPLICATION AND ORDERING INFORMATION

Honeywell L41..
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN2R-9005 0406R3-NE 12
L4191 - L6191 DUAL AQUASTAT - DIRECT IMMERSION
APPLICATION AND ORDERING INFORMATION
Application
L4191 and L6191 are dual units in which two independently
working water temperature thermostats are housed in one
cover. Each thermostat has a separate liquid filled sensing
element which fits into a common immersion well for direct
mounting into a boiler, tank or other vessel. One thermostat,
with external temperature setting dial, acts as a controller
while the other, with internal setting dial, acts as a high limit
control.
Two main types are available, one with controller and auto
recycling high limit and the other with controller and high limit
with manual reset.
Ordering information L4191
1 =Gold contacts for thermocouple applications, without jumper
2 =High limit stop at 80°C/low limit stop at 60°C
3 =High limit stop at 82°C
4 =Low limit stop at 95°C
5 =Isolated neutral terminal
6 =High limit stop at 95°C
7 =With well assembly
8 =High limit stop
9 =With jumper
10 =With push-in plug
11 =Without knob and index
Ordering information L6191
1 =Gold contacts for thermocouple applications, without jumper
2 =High limit stop at 80°C/low limit stop at 60°C
3 =High limit stop at 82°C
4 = Low limit stop at 95°C
5 = Isolated neutral terminal
6 = High limit stop at 95°C
7 = With well assembly
8 = High limit stop
9 = With jumper
10 =With push-in plug
11 = Without knob and index
O.S. number Application Temperature
range
Switch
differential (K)
Switch type Setting means Remarks
(see notes)
L4191A 2002
Controller 25 ... 95°C 4 SPST External knob 9
Limiter 25 ... 95°C 4 SPST Internal screw 9
L4191A 2010
Controller 25 ... 95°C 4 SPST External knob 7 - 9 - 10
Limiter 25 ... 95°C 4 SPST Internal screw 9
L4191B 2018
Controller 70 ... 140°C 4 SPST External knob 6
Limiter 70 ... 140°C Manual reset SPDT Internal screw 1
L4191B 2042
Controller 25 ... 95°C 4 SPST External knob 5 - 9 - 10
Limiter 25 ... 95°C Manual reset SPDT Internal screw 9 - 10
O.S. number Application Temperature
range
Switch
differential (K)
Switch type Setting means Remarks
(see notes)
L6191A 2007
Controller 40 ... 110°C
4 ... 10
(adjustable)
SPDT External knob 6 - 7 - 9
Limiter 40 ... 110°C 4 SPDT Internal screw 9
L6191A 2015
Controller 25 ... 95°C 4 SPDT External knob 3
Limiter 101°C fixed 4 SPST Internal setting 1
L6191A 2023
Controller 50 ... 95°C 4 SPDT External knob 3
Limiter 101°C fixed 4 SPST Internal screw 1
L6191B 2005
Controller 25 ... 95°C 4 SPDT External knob 7 - 9 - 10
Limiter 40 ... 110°C Manual reset SPDT Internal screw 9
L6191B 2013
Controller 40 ... 110°C 4 SPDT External knob 5 - 6 - 7 - 9
Limiter 40 ... 110°C Manual reset SPDT Internal screw 9
L6191B 2021
Controller 70 ... 140°C
4 ... 10
(adjustable)
SPDT External knob 4 - 7 - 9
Limiter 70 ... 140°C Manual reset SPDT Internal screw 9
L6191B 2047
Controller 70 ... 140°C
4 ... 10
(adjustable)
SPDT External knob 4 - 7 - 9 - 11
Limiter 70 ... 140°C Manual reset SPDT Internal screw 9
L6191B 2054
Controller 25 ... 95°C 4 SPDT External knob 7 - 10
Limiter 50 ... 95°C Manual reset SPDT Internal screw