LYNX Touch Installation and Setup Guide
- 41 -
Programming the Control
Note: If applicable, preprogrammed defaults for the LYNX Touch Control are shown on the screen unless otherwise noted.
SCREEN ACTION
System Settings
Select “System Settings”
The System displays the following options:
Entry Delay 1 Entry Delay 2
Exit Delay Backlight Timeout
Quick Arm Quick Exit Restart Exit Time
Force Bypass Exit Warning Auto Stay Arming
Use the down T arrow to scroll to the next page of options. Use the S arrow to return to
the previous page:
Lack of Usage Notify Power-Up In Previous
Display Alarm Cancel Display Exit Time
Cross Zone Delay
Cross Zone 1 Cross Zone 2
Entry Delay 1
30 Seconds
Select “Entry Delay 1”. The System scrolls between the following options:
LYNX Touch LYNX Touch (L5100CN) Canada
None None
15 Seconds 15 Seconds
30 Seconds 30 Seconds
45 Seconds 45 Seconds
60 Seconds 60 Seconds
90 Seconds 90 Seconds
2 Minutes 2 Minutes
3 Minutes
4 Minutes
UL installations: The Entry Delay must be set for a maximum of 45 seconds.
SIA: The Entry delay must be set to a minimum of 30 seconds. The sum of entry delay 1 and
the burglary abort window should not exceed 1 minute. “None” is only allowed
for use
in Commercial High-Security applications.
Entry Delay 2
30 Seconds
Select “Entry Delay 2”. The System scrolls between the following options:
LYNX Touch LYNX Touch (L5100CN) Canada
None None
15 Seconds 15 Seconds
30 Seconds 30 Seconds
45 Seconds 45 Seconds
60 Seconds 60 Seconds
90 Seconds 90 Seconds
2 Minutes 2 Minutes
3 Minutes
4 Minutes
UL installations: The Entry Delay must be set for a maximum of 45 seconds.
SIA: The Entry delay must be set to a minimum of 30 seconds. The sum of entry delay 1 and
the burglary abort window should not exceed 1 minute. “None” is only allowed
for use
in Commercial High-Security applications.
Exit Delay
60 Seconds
Select “Exit Delay”. The System toggles between the following options:
LYNX Touch LYNX Touch (L5100CN) Canada
45 Seconds None
60 Seconds 15 Seconds
90 Seconds 30 Seconds
2 Minutes 45 Seconds
60 Seconds
90 Seconds
2 Minutes
UL installations: Exit Delay must be set for a maximum of 60 seconds
SIA: The Exit Delay must be set to a minimum of 45 seconds.
Backlight Timeout
No
Select “Backlight Timeout”. The System toggles between No and 30 Seconds.