R7426D UNIVERSAL INPUT CONTROLLER
EN1B-0204GE51 R0403 10
Time Out
After approximately 10 min of inactivity (no button has been
pressed: time out) each mode returns automatically to
standard display mode. Inputs that have not been confirmed
by the SET button are ignored by the controller and old
parameter values will be retained.
Displaying Actual Values
In the standard display mode one of six actual values, can be
selected and displayed (Fig. 6) by pushing the SEL button.
The icons of the permanently displayed controller mode are
described in the following table:
Controller Mode / Status Display
Off Off - icon
On Sun - icon
A
A
Main Input X1
Main Setpoint
CTRP1
Limitation / Cascade
Input X2
Submaster / Limit Setpoint
CTRP2
Compensation
Temperature T3
Output Y1
*)
SEL
SEL
SEL
SEL
SEL
SEL
Fig. 6. Standard Display Mode
*)
The output data (Y1) are displayed between the following ranges:
Output type Control range Output range
0...10Vdc 0...100%
0...120% 0...12V (Dir)
-20...100% 12...0V (Rev)
2...10Vdc 0...100%
-25...125% 0...12V